- 49 -
User Manual ADR-out Network Analyser
Engl
ish
17) Time and date page
• The
time and date
are displayed in dd-mm-yy format
• Press
“pK”
to display the time lapsed from the start-up of the instrument,
expressed in hours and tenths of an hour
• Press
“up” (
䊱
)
to return to the starting page
Note: from the first setting onwards, the time and date will flash.
These will also flash in the peak value pages.
• The voltage and current measurements are taken in TRMS (True RMS) by
means of sampling and analogue-digital conversion.
• The following formulas are used to calculate the system values:
System voltage
V
=
V1 + V2 + V3
公
3
System current
I
=
I1 + I2 + I3
公
3
Active system power
P
= P1+P2+P3
Reactive system power
Q
= Q1+Q2+Q3
(algebraic sum)
Apparent system power
A
=
公
P
2
+
Q
2
System power factor
PF
=
P
A
Total reactive energy
E
= E1+E2+E3
Mean active system power
Er
= Er1+Er2+Er3
MEASUREMENT/CALCULATION METHOD