VDOT-ASD-400 Aspiration Detector
Velocity Detection
42
VDOT-ASD-400 Aspirating Smoke Detector User’s Manual V1
Zone Relays Function Settings
The following table is the Function Settings related to the use of zone relay board. The board must
be enabled first in item 20 (optional module) so that item 11 settings can be seen and changed
accordingly.
Ite
m
Menu
Parameter
Le
ad
N
o.
Min Max Dft
Description
Access
Level
11 Zone Relay
Configuration
Relay 1
01.
1
7
2
Relay 1~4 is Zone 1 outputs
Relay 5~8 is Zone 2 outputs
Relay 9~12 is Zone 3 outputs
Relay 13~16 is Zone 4 outputs
The relay configuration is the same as device relays.
1: ISOLATE 2: FAULT 3: ALERT
4: ACTION 5: FIRE 1
6: FIRE 2
7: AUXILIARY
Note: Relay 1/5/9/13 are Normally Closed the others are
Normally Open.
DST
Relay 2
02.
2
2
3
Relay 3
03.
1
7
4
Relay 4
04.
1
7
5
Relay 5
05.
1
7
2
Relay 6
06.
1
7
3
Relay 7
07.
1
7
4
Relay 8
08.
1
7
5
Relay 9
09.
2
2
2
Relay 10
10.
1
7
3
Relay 11
11.
1
7
4
Relay 12
12.
1
7
5
Relay 13
13.
2
2
2
Relay 14
14.
1
7
3
Relay 15
15.
1
7
4
Relay 16
16.
1
7
5
20 Optional
Module
Zone Used OP. OFF ON ON
Enable/Disable Zone
DST
Display
Used
Od. OFF ON ON
Enable/Disable Display/Programmer
Filter Used OF. OFF ON OFF
Enable/Disable Filter
Sensor
Used
OS. OFF ON OFF
Enable/Disable optional Sensor Board
Zone Relay
Used
Or. OFF ON OFF
Enable/Disable optional Zone Relay Board
Please refers to the user’s manual for the function settings using built-in display/programmer
&
Important Note:
Zone Relay Board must be enabled before it can function properly. The factory default setting of
zone relay board is disabled. Please set the zone relay board in item 20 (optional modules) to ON
to enable the module.