34
Series 49
Installation, Operating & Service Instructions
111368-04 - 1/22
10
System Start-Up and Checkout
(continued)
Table 10-4: Green LED Status Codes
Green LED
Flash
Code
Indicates
Next System Action
Recommended Service Action
OFF
No “Call for Heat”
N/A
None
Flash Fast
Power up - internal check
N/A
None
Heartbeat
Normal startup - ignition sequence
started (including prepurge)
N/A
None
4 Seconds ON
then “x” flashes
Device in run mode.
“x” = flame current to the nearest µA.
N/A
None
2
5 minute Retry Delay
- Pilot flame not detected during trial
for ignition
Initiate new trial for ignition after
retry delay completed.
If system fails to light on next trial for
ignition check gas supply, pilot burner,
spark and flame sense wiring, flame rod
contamination or out of position, burner
ground connection.
3
Recycle
- Flame failed during run
Initiate new trial for ignition. Flash
code will remain through the igni-
tion trial until flame is proved.
If system fails to light on next trial for
ignition, check gas supply, pilot burner,
flame sense wiring, contamination of
flame rod, burner ground connection.
4
Flame sensed out of sequence
If situation self corrects within
10 seconds, control returns to
normal sequence. If flame out of
sequence remains longer than
10 seconds, control will resume
normal operation 1 hour after error
is corrected.
Check for pilot flame. Replace gas valve
if pilot flame present. If no pilot flame,
cycle “Call for Heat.” If error repeats,
replace control.
6
Control Internal Error
Control remains in wait mode.
When the fault corrects, control
resumes normal operation.
Cycle “Call for Heat”. If error repeats,
replace control.
7
Flame rod shorted to ground
Control remains in wait mode.
When the fault corrects, control
resumes normal operation.
Check flame sense lead wire for damage
or shorting. Check that flame rod is
in proper position. Check flame rod
ceramic for cracks, damage or tracking.
8
Low secondary voltage supply-
(below 15.5 VAC)
Control remains in wait mode.
When the fault corrects, control
resumes normal operation.
Check transformer and AC line for prop-
er input voltage to the control. Check
with full system load on the transformer.
a
Flash Code Descriptions:
- Flash Fast: rapid blinking
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- 4 second solid on pulse followed by “x” 1 second flashes indicates flame current to the nearest µA. This is only available in
run mode.
- A single flash code number signifies that the LED flashes X times, remains off for two seconds, and then repeats the
sequence.