IG-287-EN version 03; 24/07/2020
12
Transport
General Instructions
transforma
.plur: Transformers with corrugated tank
and submerged in dielectric liquid from 3150 kVA
•
Bottom fastening elements:
located at the base of
the transformer and used for the bracing or lashing
elements for transport. (Figure 3.2)
Figure 3.2.
Bottom fastening elements
• When securing the transformer, make sure that the
lashing or bracing chains do not interfere with any of
the transformer's accessories or cooling elements.
• The fastening straps are attached to the container's
fastening elements on both sides of the transformer,
producing a symmetrical tension which is offset on both
sides.
• The connecting rods of the cooling elements must not
be used as lashing points for transport, or for any other
similar function (see Figure 3.3).
Figure 3.3.
NEVER use cooling elements to fasten for transport