IG-322-EN version 03; 22/07/2022
39
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Operation
In the switch state described, the front cover is removable,
because the pin of the front cover interlock (see Figure 5.7
and Chapter "4.9. Switch panel interlocks") has been pulled
out of the front cover.
Remove the front cover.
• Open the fastener. Turn the fastener anti-clockwise to
the end stop, using the fastener key.
• Raise the front cover up to the stop (Figure 5.6/1).
• Pull the front cover off to the front (Figure 5.6/2).
32572052
1
2
Figure 5.6.
Front cover
37250324
1
1
Locking bolt
Figure 5.7.
Front cover interlock