Emergency LED indicator & battery replacement
1
5
4
6
7
1 Owner of the building/ luminaires (or acting
party) is obliged to keep a logbook according to
NEN-EN 1838 & NEN-EN-IEC 60598-2-22.
Note
: for specific info on emergency systems see:
section 11 of this manual.
6 Disconnect the battery from the emergency module.
7 Type and/or quantity of batteries may vary as well
as the type of mounting plate.
8 Unscrew the battery from the mounting plate and
replace. Re-tighten screws and reconnect the battery
wires with the emergency module. Replace emergency
unit as described in section 6 of this manual.
2 Before installing the emergency unit or re-
placing the battery, write the installation
date onto the battery.
3 Example of emergency unit indication LED.
4 LED status indicator - table of contents.
5 Disconnect the mains before operating
the linear lighting system.
IP65
2
3
Date
Logbook
NEN-EN 1838 & NEN-EN-IEC 60598-2-22
8
LED color /
flashing
Error condition
Cause
Solution
Green /
no flashing
System OK, battery fully charged
Off
Main off, EM mode, Rest mode, test in progress
Green /
slow (0,25s on, 1,25s off)
System OK, battery is charging
Green /
fast (0,25s on, 0,25s off)
System OK, recently tested (<5 days, Australia mode only)
Red /
no flashing
Battery voltage too high or too low No battery connected
Connect battery
Wrong or bad battery connected
Replace battery
Battery pack replaced with different type
Reset driver
Red /
slow (0,25s on, 1,25s off)
Failed test due to battery
Battery end of life
Replace battery and preform duration test
Charger failure
Replace driver
Red /
fast (0,25s on, 0,25s off)
Output voltage too high or to low
Wrong LED load connected
Connect right load and preform functional test
Wrong connection
Connect right load and preform functional test
Red-Green /
fast (0,25s on, 0,25s
off)
Dali device identification
Green /
short (50ms on, 0,95s off)
Battery detection
14/16
Manual Veko linear lighting system / IP65 / V04 / 2020-09-29 / Emergency LED indicator & Battery replacement