19
6 Setup
VEGAWAVE 62 • Two-wire 8/16 mA
32255-EN-181126
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and
adjustment elements:
•
Potentiometer for adjustment of the density range (1)
•
DIL switch for mode adjustment - min./max. (2)
•
Signal lamp (5)
Note:
As a rule, always set the mode with mode switch (2) before starting
the setup of VEGAWAVE 62 . If the instrument is used in conjunction
with a signal conditioning instrument, always set the mode switch (2)
on VEGAWAVE 62 to max. mode.
The mode is selected on the signal conditioning instrument with the
mode switch.
The switching output will change if you set one of the two mode
switches afterwards. This could possibly trigger other connected
instruments or devices.
6.2 Adjustment elements
3
4
1
2
5
Fig. 12: Electronics and connection compartment - two-wire output
1 Potentiometer for adjustment of the density range
2 DIL switch for mode adjustment
3 Ground terminal
4 Connection terminals
5 Control lamp
Function/Configuration
Electronics and connec-
tion compartment