20
6 Setup
VEGAVIB 61 • Two-wire 8/16 mA
29268-EN-170315
As a default setting, the potentiometer of VEGAVIB 61 is set to the
complete right position (> 0.3 g/cm³/0.0011 lbs/in³). In very light
solids you have to turn the potentiometer to the complete left posi-
tion (0.02 … 0.1 g/cm³ or 0.0007 … 0.0036 lbs/in³). By doing this,
VEGAVIB 61 will be more sensitive and light solids can be detected
more reliably.
For instruments detecting solids in water, these settings are not ap-
plicable. The density range is preset and must not be changed.
With the mode adjustment (min./max.) you can determine the output
current.
When using a VEGATOR signal conditioning instrument, always set
the mode switch to max. mode.
In this case you select the requested mode according to the "
Function
table
" (max. - max. detection or overfill protection, min. - min.detection
or dry run detection) on the VEGATOR signal conditioning instrument.
When used on a control system, the following values apply:
•
Mode min.
– Vibrating element uncovered - 16 mA ±1 mA
– Vibrating element covered - 8 mA ±1 mA
•
Mode max.
– Vibrating element uncovered - 8 mA ±1 mA
– Vibrating element covered - 16 mA ±1 mA
Control lamp for indication of the switching status
•
green = 8 mA
•
red = 16 mA
•
red (flashing) = Failure (< 2.3 mA)
6.3 Function table
Level switch VEGAVIB 61
The following table provides an overview of the switching conditions
depending on the set mode and the level.
Mode on the sensor
Level
Signal current - Sensor Signal lamp - sensor
Max.
Overflow protection
8 mA
Green
Max.
Overflow protection
approx. 16 mA
Red
Mode adjustment (2)
Signal lamp (5)