17
6 Setup
VEGATOR 122 •
46108-EN-210714
Sensor
Controller
Level
Sensor cur-
rent
LED yellow
(output)
LED red
(fault)
Relay
any
< 3.6 mA
> 21 mA
OFF
6.4 Function table, two-point control
The following charts provide an overview of the switching conditions
depending on the set mode and the level.
Note:
The switching conditions in the tables are only valid if the mode
switch on the sensor is set to "
Max.
".
Sensor
Controller
Level
Sensor cur-
rent
LED yellow
(output)
LED red
(fault)
Relay
approx. 8 mA
approx. 8 mA
ON
approx. 8 mA
approx. 16 mA
ON
approx. 16 mA
approx. 16 mA
OFF
approx. 8 mA
approx. 16 mA
OFF
approx. 8 mA
approx. 8 mA
ON
any
< 3.6 mA
> 21 mA
OFF
Overfill protection, two-
point control