6 Setup

VEGATOR 122 • 

46108-EN-210714

is checked and evaluated when switch-on pulse monitoring is acti-

vated. If this does not correspond to the definition or is completey 

missing, the VEGATOR 122 displays a fault. A function test is only 

triggered by pressing the test key. This function test is not carried out 

automatically when switching on the VEGATOR 122. 

Note:

When connecting sensors without this defined switching sequence, 

the switch-on monitoring must be deactivated.

With these switches you can delay the changeover of the relays by 

the set time. This can be useful, e.g. with fluctuating product surfaces, 

for preventing unwanted switching commands. The switch-on/off 

delays can be set independently of each other. If both switches, e.g. 

of the switch-on delay, are activated, the times sum up. Delays of 2, 6 

or 8 seconds can thus be adjusted.

Information:

Keep in mind that the switching delay of the sensor and controller 

accumulate.

The following functionalities can be selected via this switch:

• 

Single point control (double channel level detection with one sen-

sor each and the same switch on/switch off point)

• 

Two-point control (level detection with two sensors and different 

switch on/switch off points)

As opposed to single point control, two-point control allows the 

switch-on and switch-off points to be set at different locations (hyster-

esis). Through the installation or the distance of the two sensors, the 

hysteresis can be defined individually. Here, the max. level must be 

set to sensor input 1, the min. level to sensor input 2.
The two-point control is used for example when filling and emptying 

is carried out via a pump. The filling of a vessel can be for example 

switched on at 10 % and switched off again at 90 %. The output of the 

second channel behaves identically like the first channel provided the 

same mode is set. By changing the mode, the function of the relays 

can be inverted.

When level switches VEGAVIB, VEGAWAVE, VEGASWING in two-

wire version are connected, a function test can be carried out. The 

test key is recessed behind the front plate of the controller. Press the 

test key for at least one second with a suitable object (screwdriver, 

pen, etc.).

Note:

Keep in mind that downstream connected devices are activated dur-

ing the function test. This allows you to check the correct function of 

the complete measuring system.
By pushing the test key, the circuit to the sensor is interrupted and a 

restart of the sensor is initiated. Through this, the conditions fault sig-

nal, empty and full alarm are simulated. The complete test procedure 

takes approx. 5 seconds. After correct function, the red failure LED 

Switch-on/Switch-off 

delay

Two-point control

Test key

Содержание VEGATOR 122

Страница 1: ...Operating Instructions Double channel controller for level detection for 8 16 mA sensors VEGATOR 122 Document ID 46108...

Страница 2: ...structions 9 5 Connecting to power supply 10 5 1 Preparing the connection 10 5 2 Connection procedure 11 5 3 Wiring plan 12 6 Setup 13 6 1 Adjustment system 13 6 2 Adjustment elements 13 6 3 Function...

Страница 3: ...210714 10 4 Trademark 27 Supplementary documentation Information Supplementary documents appropriate to the ordered version come with the delivery You can find them listed in chapter Product descrip...

Страница 4: ...tering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successful work Note This symbol ind...

Страница 5: ...a state of the art instrument complying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi b...

Страница 6: ...n Canada shall comply with the relevant requirements of the Canadian Electrical Code 2 6 Safety instructions for Ex areas For applications in explosion proof areas Ex only devices with cor responding...

Страница 7: ...can find all via your smartphone Scan the QR code on the type label of the device or Enter serial number manually in the VEGA Tools app available free of charge in the respective stores 3 2 Principle...

Страница 8: ...ling companies Transport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device The delivery must be checke...

Страница 9: ...und the ventilation slots there must be a distance of at least 2 cm to the next component VEGATOR 122 in Ex version is a corresponding intrinsically safe in strument and must not be installed in hazar...

Страница 10: ...of EN 61326 for industrial areas shielded cable should be used Make sure that the cable used has the required temperature resist ance and fire safety for max occurring ambient temperature Connect the...

Страница 11: ...d as follows 1 Mount the instrument as described in the previous chapter 2 Connect sensor cable 1 to terminal 1 2 and where applicable connect the shielding 3 Connect sensor cable 2 to terminal 4 5 an...

Страница 12: ...1 8 16 mA max level with two point control 2 Sensor circuit channel 2 8 16 mA min level with two point control 3 Relay output channel 1 4 Relay output channel 2 5 Voltage supply Information The conne...

Страница 13: ...ignal lamps LEDs 4 Hinged front cover 6 2 Adjustment elements Control lamps LED in the front plate indicate operation switching status and fault signal Green Operating control lamp Mains voltage on in...

Страница 14: ...delay 6 seconds 7 Two point control On Off 8 Mode min max adjustment channel 2 The requested operating mode is set with the min max switch min detection i e dry run protection or max detection i e ov...

Страница 15: ...control two point control allows the switch on and switch off points to be set at different locations hyster esis Through the installation or the distance of the two sensors the hysteresis can be def...

Страница 16: ...to WHG 6 3 Function table Point level The following table provides an overview of the switching conditions depending on the set mode and the level Note The switching conditions in the tables are only...

Страница 17: ...onditions depending on the set mode and the level Note The switching conditions in the tables are only valid if the mode switch on the sensor is set to Max Sensor Controller Level Sensor cur rent LED...

Страница 18: ...evel Sensor cur rent LED yellow output LED red fault Relay approx 8 mA approx 8 mA OFF approx 8 mA approx 16 mA OFF approx 16 mA approx 16 mA ON approx 8 mA approx 16 mA ON approx 8 mA approx 8 mA OFF...

Страница 19: ...many cases the causes can be determined this way and faults can be easily rectified Depending on the reason for the fault and the measures taken the steps described in chapter Setup must be carried o...

Страница 20: ...or or sensor cable Reconnect the sensor cable to the controller disconnect the sensor and replace it with a 1 k resistor If the fault signal does not disappear then the sensor cable is broken replace...

Страница 21: ...ut one form per instrument Clean the instrument and pack it damage proof Attach the completed form and if need be also a safety data sheet outside on the packaging Ask the agency serving you to get th...

Страница 22: ...te of chapters Mounting and Connecting to voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal The device is made of recyclable materials For this reason it should be disposed...

Страница 23: ...und on our homepage 9 3 SIL conformity optional Instruments with SIL option fulfill the requirements of functional safety according to IEC 61508 You can find further information in the sup plied Safet...

Страница 24: ...re cross section 0 25 mm AWG 23 2 5 mm AWG 12 Voltage supply Operating voltage Nominal voltage AC 24 230 V 15 10 50 60 Hz Nominal voltage DC 24 65 V 15 10 Max power consumption 3 W 8 VA Sensor input Q...

Страница 25: ...conditions Vibrations oscillations Class 4M4 acc to IEC 60721 3 4 1 g 4 200 Hz Impacts mechanical shock Class 6M4 acc to IEC 60721 3 6 10 g 11 ms 30 g 6 ms 50 g 2 3 ms Electrical protective measures...

Страница 26: ...ed approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded by entering the serial number of your instrument into the search field under ww...

Страница 27: ...www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de produc...

Страница 28: ...4 E Ex version 9 F Fault Fault signal 19 Fault rectification 19 G Grounding 10 H Hysteresis 15 L LEDs 13 M Mode 14 O Overflow protection 14 P Potential equalisation 10 Protection rating 9 Q QR code 7...

Страница 29: ...29 Notes VEGATOR 122 46108 EN 210714...

Страница 30: ...30 Notes VEGATOR 122 46108 EN 210714...

Страница 31: ...31 Notes VEGATOR 122 46108 EN 210714...

Страница 32: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Отзывы: