21
4 Mounting
VEGASOURCE 84 • Source holder
1008681-EN-230810
Due to the special design, the lid can only be put on in such a way
that the visible indication plate on the source holder shows the current
switching status.
Measurement of the local dose rate
After mounting, i.e. as soon as the radioactive emitter is mounted in
the source holder, the local dose rate in the area of the source holder
and the detector must be measured in µSv/h (mR/h).
Caution:
Depending on the respective installation, radiation can also leak out
of the beam exit channel due to scattering. Such stray radiation must
be shielded off with additional lead or steel sheets. All control and off-
limit areas must be rendered inaccessible and provided with warning
signs.
Behaviour with empty vessel
Caution:
After technically correct mounting, the control area around an empty
vessel must be measured for radioactivity and if there is any, the area
must be cordoned off and marked. Possible ways of access to the
inside of the vessel must be reliably closed off and marked with a
warning sign "Radioactive".
The responsible radiation safety officer can allow access after having
checked the safety measures with switched-off source holder.
If work must be carried out in and on the vessel, it is absolutely neces-
sary to switch off the radiation on the source holder.
Installation control
Содержание VEGASOURCE 84
Страница 1: ...Operating Instructions VEGASOURCE 84 Source holder Document ID 1008681...
Страница 3: ...3 Contents VEGASOURCE 84 Source holder 1008681 EN 230810 Editing status 2023 08 10...
Страница 49: ...49 10 Supplement VEGASOURCE 84 Source holder 1008681 EN 230810 10 3 Manufacturer declaration...
Страница 52: ...52 Notes VEGASOURCE 84 Source holder 1008681 EN 230810...
Страница 53: ...53 Notes VEGASOURCE 84 Source holder 1008681 EN 230810...
Страница 54: ...54 Notes VEGASOURCE 84 Source holder 1008681 EN 230810...
Страница 55: ...55 Notes VEGASOURCE 84 Source holder 1008681 EN 230810...