9
5 Set up with the display and adjustment module PLICSCOM
VEGASON 63 • Four-wire 4 … 20 mA/HART
51864-EN-210616
5 Set up with the display and adjustment
module PLICSCOM
5.1 Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
and removed again at any time. It is not necessary to interrupt the
voltage supply.
Proceed as follows:
1. Unscrew the housing lid
2. Place the display and adjustment module in the desired position
on the electronics (four positions in 90° offset can be selected)
and turn to the right until it clicks into place.
3. Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.
Fig. 5: Insert display and adjustment module in the single chamber housing
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher lid with an
inspection glass is required.
5.2 Setup steps
1. Go to the menu "
Basic adjustment
" via the display and adjust-
ment module.
Mount/dismount display
and adjustment module
Set parameters