7 Supplement
7.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included in delivery are valid for
approved instruments (e.g. with Ex approval). These data can differ from the data listed herein, for
example regarding the process conditions or the voltage supply.
All approval documents can be downloaded from our homepage.
Input variable
Measured variable
distance between lower edge of the transducer and
medium surface
Measuring range
Ʋ
Liquids
up to 8 m (26.25 ft)
Ʋ
Bulk solids
up to 3.5 m (11.48 ft)
Dead zone
0.4 m (1.312 ft)
Electromechanical data - version IP66/IP67 and IP66/IP68 (0.2 bar)
Options of the cable entry
Ʋ
Cable entry
M20 x 1.5; ½ NPT
Ʋ
Cable gland
M20 x 1.5; ½ NPT
Ʋ
Blind plug
M20 x 1.5; ½ NPT
Ʋ
Closing cap
½ NPT
Wire cross-section (spring-loaded terminals)
Ʋ
Massive wire, stranded wire
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ
Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Voltage supply
Operating voltage
9 … 32 V DC
Operating voltage U
B
with lighting
switched on
12 … 32 V DC
Power supply by/max. number of sensors
32