4 Mounting
VEGAPULS WL 61 • 4 … 20 mA/HART - two-wire
38061-EN-121011
Fig. 16: Mounting of the radar sensor on vessels with conical bottom
Do not mount the instrument in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 17: Mounting of the radar sensor with inflowing medium
Approximate values of the socket heights are shown in the following
illustration. The socket end should be smooth and burr-free, if possi-
ble also rounded. After mounting, you have to carry out a false signal
memory during the parameter adjustment.
Inflowing medium
Socket