14

4 Connecting to power supply and bus system

VEGAPULS SR 68 • Modbus and Levelmaster protocol

47164-EN-180226

Information:

The connection of an external display and adjustment unit is not pos

-

sible with this double chamber housing.

+

+

power   supply

MODBUS

D0

D1

IS GND

USB

1

2

4

3

1

3 4 5

2

off on

(  )

)

(-)

(-)

Fig. 9: Terminal compartment
1  USB interface

2  Slide switch for integrated termination resistor (120 Ω)

3  Modbus signal

4  Voltage supply

Terminal

Function

Polarity

1

Voltage supply

+

2

Voltage supply

-

3

Modbus signal D0

+

4

Modbus signal D1

-

5

Function ground when installing ac-

cording to CSA (Canadian Standards 

Association)

Terminal compartment

Содержание VEGAPULS SR 68

Страница 1: ...Quick setup guide Radar sensor for continuous level measurement of bulk solids VEGAPULS SR 68 Modbus and Levelmaster protocol Document ID 47164...

Страница 2: ...er supply and bus system 12 4 1 Connecting 12 4 2 Wiring plan 13 5 Set up the sensor with the display and adjustment module 15 5 1 Insert display and adjustment module 15 5 2 Parameter adjustment 15 5...

Страница 3: ...with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi ble for the trouble free operation of the...

Страница 4: ...the electromag netic compatibility to other instruments must be ensured by suitable measures 1 6 NAMUR recommendations NAMUR is the automation technology user association in the process industry in G...

Страница 5: ...metal reinforced fiberglass or concrete Changes or modifications not expressly approved by the manufac turer could void the user s authority to operate this equipment 1 9 Environmental instructions P...

Страница 6: ...ce protection class 14 ID numbers instrument documentation 15 Reminder to observe the instrument documentation The type label contains the serial number of the instrument With it you can find the foll...

Страница 7: ...EGAPULS SR 68 Modbus and Levelmaster protocol 47164 EN 180226 This operating instructions manual applies to the following instrument versions Hardware from 2 1 0 Software from 4 5 1 Scope of this oper...

Страница 8: ...of the antenna 5 Remove the parabolic antenna 4 axially 6 Mount sensor flange on the adapter flange and fasten it tightly 7 Check if the O ring seal is present on the connection piece and make sure it...

Страница 9: ...gainst falling off 4 Retighten the antenna with hexagon screws to the antenna socket max torque see chapter Technical data Note The radar sensor with rinsing air connection or with antenna exten sion...

Страница 10: ...t damaged Note A damaged O ring seal must be replaced FKM SHS FPM 70C3 GLT FFKM Kalrez 6375 8 Remount the parabolic antenna 4 9 Fasten compression nut 2 with a wrench width across flats 41 max torque...

Страница 11: ...r protocol 47164 EN 180226 ca 10 mm 200 mm 7 87 Fig 5 Distance of the antenna to the vessel wall vessel ceiling 2 Note min socket diameter depending on the socket length 3 Note the instructions for se...

Страница 12: ...should hear it snap in Proceed as follows 1 Unscrew the housing lid 2 Loosen compression nut of the cable gland and remove blind plug 3 Remove approx 10 cm 4 in of the cable mantle signal output strip...

Страница 13: ...cable glands The seal ring must completely encircle the cables 10 Screw the housing lid back on The electrical connection is finished Information The terminal blocks are pluggable and can be removed...

Страница 14: ...chamber housing power supply MODBUS D0 D1 IS GND USB 1 2 4 3 1 3 4 5 2 off on Fig 9 Terminal compartment 1 USB interface 2 Slide switch for integrated termination resistor 120 3 Modbus signal 4 Volta...

Страница 15: ...ent module on the electronics in the desired position and turn it to the right until it snaps in 3 Screw housing lid with inspection window tightly back on Disassembly is carried out in reverse order...

Страница 16: ...nce from the sensor to the product surface For indication of the real level an allocation of the measured distance to the percentage height must be carried out 2 1 3 100 0 1 m 39 37 35 m 1378 Fig 11 P...

Страница 17: ...th the current echo curve The following circumstances cause interfering reflections and can influence the measurement High mounting sockets Vessel internals such as struts Agitators Buildup or welded...

Страница 18: ...vessel Extend is used to extend an already created false signal suppres sion This is useful if a false signal suppression was carried out with too high a level and not all false signals could be detec...

Страница 19: ...suring cell Measuring cell tempera ture in C Metallic measuring cell Electronics temperature in C Display format 1 and 2 Number of positions after the decimal point auto matically Backlight Switched o...

Страница 20: ...Lin percent Level Current output Adjustment 0 100 correspond to 4 20 mA Current out put 2 Current output Meas vari able Measuring cell temperature ceramic measuring cell Current output Adjustment 0 1...

Страница 21: ...approval These data can differ from the data listed herein for example regarding the process conditions or the voltage supply Electromechanical data version IP 66 IP 67 Cable gland M20 x 1 5 or NPT Wi...

Страница 22: ...22 Notes VEGAPULS SR 68 Modbus and Levelmaster protocol 47164 EN 180226...

Страница 23: ...23 Notes VEGAPULS SR 68 Modbus and Levelmaster protocol 47164 EN 180226...

Страница 24: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: