52
14 Supplement
VEGAPULS C 23 • Modbus and Levelmaster protocol
58349-EN-200806
Register Number Register Name
Data type
Access
Note
1400
Status
enum8
ro
See Register 100
1402
PV
float32
ro
Primary Variable in Byte Order CDAB
1414
SV
float32
ro
Secondary Variable in Byte Order CDAB
1426
TV
float32
ro
Third Variable in Byte Order CDAB
1438
QV
float32
ro
Quarternary Variable in Byte Order CDAB
2000
Status
enum8
ro
See Register 100
2002
PV
float32
ro
Primary Variable in Byte Order ABCD (Big Endian)
2004
SV
float32
ro
Secondary Variable in Byte Order ABCD (Big Endian)
2006
TV
float32
ro
Third Variable in Byte Order ABCD (Big Endian)
2008
QV
float32
ro
Quarternary Variable in Byte Order ABCD (Big Endian)
2100
Status
enum8
ro
See Register 100
2102
PV
float32
ro
Primary Variable in Byte Order DCBA (Little Endian)
2104
SV
float32
ro
Secondary Variable in Byte Order DCBA (Little Endian)
2106
TV
float32
ro
Third Variable in Byte Order ABCD DCBA (Little Endian)
2108
QV
float32
ro
Quarternary Variable in Byte Order DCBA (Little Endian)
2200
Status
enum8
ro
See Register 100
2202
PV
float32
ro
Primary Variable in Byte Order BACD (Middle Endian)
2204
SV
float32
ro
Secondary Variable in Byte Order BACD (Middle Endian)
2206
TV
float32
ro
Third Variable in Byte Order BACD (Middle Endian)
2208
QV
float32
ro
Quarternary Variable in Byte Order BACD (Middle Endian)