6 Supplement
VEGAPULS 61 • Profibus PA
47106-EN-161104
6 Supplement
6.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Ex approval). These data can differ from the data listed herein, for example regarding the process
conditions or the voltage supply.
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
Ʋ Cable entry
M20 x 1.5, ½ NPT
Ʋ Cable gland
M20 x 1,5; ½ NPT (cable ø see below table)
Ʋ Blind plug
M20 x 1.5; ½ NPT
Ʋ Closing cap
½ NPT
Material ca-
ble gland
Material seal
insert
Cable diameter
4.5 … 8.5 mm
5 … 9 mm
6 … 12 mm
7 … 12 mm
10 … 14 mm
PA
NBR
–
●
●
–
●
Brass, nickel-
plated
NBR
●
●
●
–
–
Stainless
steel
NBR
–
●
●
–
●
Wire cross-section (spring-loaded terminals)
Ʋ Massive wire, stranded wire
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Voltage supply
Operating voltage U
B
Ʋ Non-Ex instrument
9 … 32 V DC
Ʋ Ex-ia instrument - Power supply
FISCO model
9 … 17.5 V DC
Ʋ Ex-ia instrument - Power supply
ENTITY model
9 … 24 V DC
Ʋ Ex-d-ia instrument
16 … 32 V DC
Operating voltage U
B
- illuminated display and adjustment module
Ʋ Non-Ex instrument
13.5 … 32 V DC
Ʋ Ex-ia instrument - Power supply
FISCO model
13.5 … 17.5 V DC
Ʋ Ex-ia instrument - Power supply
ENTITY model
13.5 … 24 V DC
Ʋ Ex-d-ia instrument
No lighting possible (integrated ia barrier)
Number of sensors per DP/PA segment coupler, max.
Ʋ Non-Ex
32