31
10 Diagnostics and servicing
VEGAPULS 42 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
1016153-EN-230316
under the menu item "
Diagnostics
" via the respective adjustment
module.
The status messages are divided into the following categories:
•
Failure
•
Function check
•
Out of specification
•
Maintenance required
and explained by pictographs:
4
1
2
3
Fig. 16: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance required - blue
Malfunction (Failure):
Due to a malfunction in the instrument, a fault signal is output.
This status message is always active. It cannot be deactivated by the
user.
Function check:
The instrument is being worked on, the measured value is temporarily
invalid (for example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an instrument specification
was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument function is limited. The
measurement is affected, but the measured value is still valid. Plan in
maintenance for the instrument because a failure is expected in the
near future (e.g. due to buildup).
This status message is inactive by default.
Code
Text message
Cause
Rectification
F013
no measured value
available
No measured value in the switch-on
phase or during operation
Check or correct installation and/or pa-
rameter settings
Clean the antenna system