DCS
value is represented by two words
.
T
he
fi
rst word
contains the real
PC
/
DCS
value
,
the next higher word the
corresponding status information
.
I
n the speci
fi
cation the term
register word is also used instead of word
.
T
he
fi
ling of measured values in the temporary memory is
always sorted according to
PC
/
DCS
output number
.
T
he
following chart shows the addressing of the temporary memory
via
M
odbus
.
R
egister address in
M
odicon
T
emporary memory of
VEGAMET
/
PLICSRA
-
DIO
(
1
word
=
2
byte
)
30001
PC
/
DCS
output
1
:
M
easured value
30002
PC
/
DCS
output
1
:
S
tatus
30003
PC
/
DCS
output
2
:
M
easured value
30004
PC
/
DCS
output
2
:
S
tatus
30005
PC
/
DCS
output
3
:
M
easured value
30006
PC
/
DCS
output
3
:
S
tatus
30007
PC
/
DCS
output
4
:
M
easured value
30008
PC
/
DCS
output
4
:
S
tatus
30009
PC
/
DCS
output
5
:
M
easured value
30010
PC
/
DCS
output
5
:
S
tatus
30011
PC
/
DCS
output
6
:
M
easured value
30012
PC
/
DCS
output
6
:
S
tatus
R
egister address in
M
odicon
T
emporary memory of
VEGASCAN
(
1
word
=
2
byte
)
30001
PC
/
DCS
output
1
:
M
easured value
30002
PC
/
DCS
output
1
:
S
tatus
30003
PC
/
DCS
output
2
:
M
easured value
30004
PC
/
DCS
output
2
:
S
tatus
30005
PC
/
DCS
output
3
:
M
easured value
30006
PC
/
DCS
output
3
:
S
tatus
30007
PC
/
DCS
output
4
:
M
easured value
30008
PC
/
DCS
output
4
:
S
tatus
30009
PC
/
DCS
output
5
:
M
easured value
30010
PC
/
DCS
output
5
:
S
tatus
30011
PC
/
DCS
output
6
:
M
easured value
4
M
odbus
-
TCP
,
VEGA ASCII
protocol
-
VEGAMET
624
/
625
,
VEGASCAN
693
,
PLICSRADIO
F
unction as
M
odbus
-
TCP
server
30768
-
EN
-
070730
Содержание VEGAMET 624
Страница 37: ...Modbus TCP VEGA ASCII protocol VEGAMET 624 625 VEGASCAN 693 PLICSRADIO 37 VEGA ASCII protocol 30768 EN 070730...
Страница 38: ...38 Modbus TCP VEGA ASCII protocol VEGAMET 624 625 VEGASCAN 693 PLICSRADIO VEGA ASCII protocol 30768 EN 070730...
Страница 39: ...Modbus TCP VEGA ASCII protocol VEGAMET 624 625 VEGASCAN 693 PLICSRADIO 39 VEGA ASCII protocol 30768 EN 070730...