IP
address
F
ix
IP
address
▼
LAN
/
I
nternet
IP
address
:
192
.
168
.
200
.
200
S
ubnet mask
:
255
.
255
.
255
.
0
C
hange
?
à
E
nter the values via the appropriate keys and save your settings
with
[
OK
]
.
D
isconnect brie
fl
y the operating voltage so that the
modi
fi
ed settings become e
ff
ective
.
D
ate and time can be entered in this menu item for instruments with
integrated
RS
232
/
E
thernet interface
.
T
hese time settings are bu
ff
ered
in case of power failure for approx
.
3
days
.
T
ime
/
D
ate
8
:
40
28
.
09
.
2004
à
E
nter the values via the appropriate keys and save your settings
with
[
OK
]
.
VEGAMET
624
can process measured values from
4
…
20
m
A
/
HART
sensors via analogue communication as well as via digital
HART
protocol
.
A
nalogue
4
…
20
m
A
transmission
I
n the standard setting of
VEGAMET
624
the measured value
transmission is carried out via analogue
4
…
20
signal
.
A
n adjustment
in the sensor in
fl
uences directly the input variable of
VEGAMET
624
.
O
nly carry out the adjustment on one instrument
,
either on
VEGAMET
624
or on the sensor
.
T
he adjustment in
VEGAMET
624
is always
carried out in m
A
(
analogue transmission
).
D
igital
HART
transmission
F
or transmission via
HART
,
VEGAMET
624
must be informed which
sensor value should be used for further processing
.
D
epending on the
sensor type
,
this can be distance
,
pressure or temperature
.
W
ith all
VEGA HART
sensors
,
always the unchanged initial value of the sensor
is transmitted to
VEGAMET
624
.
T
hus
,
the adjustment must always
carried out on
VEGAMET
624
,
never on the sensor
.
D
i
ff
erent
parameters and meas
.
units are available
.
D
evice settings
-
T
ime
/
D
ate
M
easurement loop
-
I
n
-
put
VEGAMET
624
•
4
…
20
m
A
/
HART
signal conditioning instrument
19
6
S
etup with the integrated indicating and adjustment unit
28969
-
EN
-
091116