I
nformation
:
V
ia the slide switch on the rear of the instrument you can
switch over between active and passive operation of the
measuring data input
:
l
I
n active mode
,
VEGAMET
381
E
x provides the power for
the connected sensors
.
P
ower supply and measurement
data are transmitted over the same two
-
wire cable
.
T
his
mode is provided for connection of transmitters without
separate power supply
(
sensors in two
-
wire version
).
l
I
n passive mode the sensors are not powered
,
only the
measured value is transmitted
.
T
his input is for connection
of transmitters with own
,
separate voltage supply
(
sensors
in four
-
wire version
).
T
he
VEGAMET
381
E
x can be also
connected into the existing circuit like a normal current
meter
.
T
he position of the slide switch also in
fl
uences the precondi
-
tions for
E
x implementation
.
T
ake note of the type approval
certi
fi
cate or the conformity certi
fi
cate of
VEGAMET
381
E
x
.
T
ip
:
F
or parameter adjustment of connected
HART
sensors
,
the
sockets are integrated in the terminals of the meas
.
data input
.
A VEGACONNECT
can be directly plugged in without the
need of an additional
HART
resistor
.
14
VEGAMET
381
E
x
-
4
…
20
m
A
signal conditioning instrument
C
onnecting to voltage supply
30418
-
EN
-
060925