5 Set up with the display and adjustment module
VEGAFLEX 86 • 4 … 20 mA/HART - two-wire
47615-EN-150102
1
2
Fig. 8: Installing the display and adjustment module in the double chamber
housing
1 In the electronics compartment
2 In the terminal compartment
Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.
5.2 Parameter adjustment
1. In this menu item you can select the application. You can choose
between level and interface measurement.
2. In the menu item "
Medium - Dielectric constant
" you can define
the type of medium (medium).
3. Carry out the adjustment in the menu items "
Min. adjustment
" and
"
Max. adjustment
".
4. A "
Linearization
" is recommended for all vessels in which the
vessel volume does not increase linearly with the level - e.g. in a
horizontal cylindrical or spherical tank. Activate the appropriate
curve.
5. A "
False signal suppression
" detects, marks and saves the false
signals so that they are no longer taken into account for level
Set parameters