9
3 Mounting
VEGAFLEX 82 • 4 … 20 mA/HART - four-wire
47593-EN-140324
ø >160mm
(ø >6.3")
Fig. 4: Installation in concrete silo
If possible, avoid sockets. Mount the sensor flush with the vessel top.
If this is not possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally be
used. They can, however, increase the upper blocking distance (dead
band). Check if this is relevant for your measurement.
In such cases, always carry out a false signal suppression after instal-
lation. You can find further information under "
Setup procedure
".
h
d
d
h
DN40 ... DN150
> DN150 ... DN200
150
100
_<
_<
Fig. 5: Mounting socket
Socket