2 Product description

VEGAFLEX 82 • 4 … 20 mA/HART - four-wire

47593-EN-140324

2  Product description

2.1  Configuration

The type label contains the most important data for identification and 

use of the instrument:

2

1

13

14

15

16

12

11

5

3

6

4

7

8

9

10

Fig. 1: Layout of the type label (example)
1  Instrument type

2  Product code

3 Approvals

4  Power supply and signal output, electronics

5  Protection rating

6  Probe length

7  Process and ambient temperature, process pressure

8  Material, wetted parts

9  Hardware and software version

10  Order number

11  Serial number of the instrument

12  Symbol of the device protection class

13  ID numbers, instrument documentation

14  Reminder to observe the instrument documentation

15  Notified authority for CE marking

16  Approval directives

The type label contains the serial number of the instrument. With it 

you can find the following instrument data on our homepage:

• 

Product code (HTML)

• 

Delivery date (HTML)

• 

Order-specific instrument features (HTML)

• 

Operating instructions and quick setup guide at the time of ship-

ment (PDF)

• 

Order-specific sensor data for an electronics exchange (XML)

• 

Test certificate (PDF) - optional

Go to www.vega.com, "

VEGA Tools

" and "

Instrument search

". Enter 

the serial number.
Alternatively, you can access the data via your smartphone:

• 

Download the smartphone app "

VEGA Tools

" from the "

Apple App 

Store

" or the "

Google Play Store

"

Type label

Serial number - Instru-

ment search

Содержание VEGAFLEX 82

Страница 1: ...Quick setup guide TDR sensor for continuous level measurement of bulk solids VEGAFLEX 82 4 20 mA HART four wire Rod and cable probe Document ID 47593...

Страница 2: ...wer supply 4 1 Connection 11 4 2 Wiring plan double chamber housing 12 5 Set up with the display and adjustment module 5 1 Insert display and adjustment module 14 5 2 Parameter adjustment Quick setup...

Страница 3: ...omplying with all prevailing regulations and guidelines The instrument must only be operated in a technically flawless and reliable condition The operator is responsible for the trouble free operation...

Страница 4: ...pted as the standard in field instrumentation The device fulfills the requirements of the following NAMUR recom mendations NE 21 Electromagnetic compatibility of equipment NE 43 Signal level for malfu...

Страница 5: ...ection class 13 ID numbers instrument documentation 14 Reminder to observe the instrument documentation 15 Notified authority for CE marking 16 Approval directives The type label contains the serial n...

Страница 6: ...6 2 Product description VEGAFLEX 82 4 20 mA HART four wire 47593 EN 140324 Scan the Data Matrix code on the type label of the instrument or Enter the serial number manually in the app...

Страница 7: ...ssels 3 2 Mounting instructions Mount VEGAFLEX 82 in such a way that the distance to vessel instal lations or to the vessel wall is at least 300 mm 12 in In non metallic vessels the distance to the ve...

Страница 8: ...t contact with the process fitting When installing rod or cable probes without metal vessel wall e g in plastic vessels the measured value can be influenced by strong electromagnetic fields emitted in...

Страница 9: ...sockets with small diameter Higher sockets or sockets with a bigger diameter can generally be used They can however increase the upper blocking distance dead band Check if this is relevant for your me...

Страница 10: ...2 4 20 mA HART four wire 47593 EN 140324 When welding the socket make sure that the socket is flush with the vessel top 1 2 Fig 6 Socket must be installed flush 1 Unfavourable installation 2 Socket fl...

Страница 11: ...ew the housing cover 2 Loosen compression nuts of the cable glands 3 Remove approx 10 cm 4 in of the cable mantle signal output strip approx 1 cm 0 4 in insulation from the ends of the indi vidual wir...

Страница 12: ...The electrical connection is finished Information The terminal blocks are pluggable and can be removed from the housing insert To do this lift the terminal block with a small screwdriv er and pull it...

Страница 13: ...on IS GND 5 1 L N 2 6 7 8 Fig 9 Connection compartment with double chamber housing with low voltage Terminal Function Polarity 1 Voltage supply L 2 Voltage supply N 5 4 20 mA output active 6 4 20 mA o...

Страница 14: ...d by 90 It is not necessary to interrupt the power supply Proceed as follows 1 Unscrew the housing cover 2 Place the display and adjustment module in the requested posi tion onto the electronics and t...

Страница 15: ...p To quickly and easily adapt the sensor to the application select the menu item Quick setup in the start graphic on the display and adjustment module You can find Extended adjustment in the next sub...

Страница 16: ...in adjustment for the level Enter the suitable distance value in m for the empty vessel e g distance from the flange to the probe end corresponding to the per centage value The distance refers tot he...

Страница 17: ...M20 x 1 5 or NPT Wire cross section spring loaded terminals Massive wire cord 0 2 2 5 mm AWG 24 14 Stranded wire with end sleeve 0 2 1 5 mm AWG 24 16 Voltage supply Operating voltage Version for low v...

Страница 18: ...18 Notes VEGAFLEX 82 4 20 mA HART four wire 47593 EN 140324...

Страница 19: ...19 Notes VEGAFLEX 82 4 20 mA HART four wire 47593 EN 140324...

Страница 20: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: