0
s
E
nter the requested parameter via the appropriate keys
,
save
your settings and jump to the next menu item with the
[-
>
]
key
.
A
linearization is necessary for all vessels in which the vessel
volume does not increase linearly with the level
-
e
.
g
.
with a
cylindrical or spherical tank
-
and the indication or output of the
volume is required
.
C
orresponding linearization curves are
preprogrammed for these vessels
.
T
hey represent the
correlation between the level percentage and vessel volume
.
B
y activating the appropriate curve
,
the volume percentage of
the vessel is displayed correctly
.
I
f the volume should not be
displayed in percent but e
.
g
.
in l or kg
,
a scaling can be also
set in the menu item
"
D
isplay
"
.
L
inearisation curve
linear
E
nter the requested parameter via the appropriate keys
,
save
your settings and jump to the next menu item with the
[-
>
]
key
.
C
aution
:
N
ote the following
,
if
VEGAFLEX
65
is used as part of an
over
fi
ll protection system according to
WHG
:
I
f a linearisation curve is selected
,
the measuring signal is no
longer compulsorily linear proportional to the level
.
T
his must
be taken into consideration by the user
,
particularly when
adjusting the switching point on the level switch
.
I
n this menu item you can enter an unambiguous designation
for the sensor
,
e
.
g
.
the measurement loop name or the tank or
product designation
.
I
n digital systems and in the documen
-
tation of larger plants
,
a singular designation should be entered
for exact identi
fi
cation of individual measuring sites
.
S
ensor
-
TAG
S
ensor
L
inearisation curve
S
ensor
-
TAG
30
VEGAFLEX
65
•
4
…
20
m
A
/
HART
6
S
et up with the indicating and adjustment module
PLICSCOM
31845
-
EN
-
080716