73
12 Supplement
VEGADIF 85 • Profibus PA
53569-EN-230814
Measuring ranges in kPa
Measuring range
Nominal range
Max. adjustment range
1 kPa
-1 kPa … +1 kPa
-1.2 kPa … +1.2 kPa
3 kPa
-3 kPa … +3 kPa
-3.6 kPa … +3.6 kPa
10 kPa
-10 kPa … +10 kPa
-12 kPa … +12 kPa
50 kPa
-50 kPa … +50 kPa
-60 kPa … +60 kPa
300 kPa
-300 kPa. … +300 kPa
-360 kPa … +360 kPa
1600 kPa
-1600 kPa … +1600 kPa
-1920 kPa … +1920 kPa
4000 kPa
-4000 kPa … +4000 kPa
-4800 kPa … +4800 kPa
Turn Down
Maximum permissible Turn Down
Unlimited (recommended up to 20 : 1)
Turn down (TD) is the relation nominal measuring range/adjusted span.
Switch-on phase
Start-up time with operating voltage U
B
Ʋ ≥ 12 V DC
≤ 9 s
Ʋ
< 12 V DC
≤ 22 s
Output variable
Output signal
digital output signal, Profibus protocol
Transmission rate
31.25 Kbit/s
Instrument address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ
1. FB
Primary Value (pressure linearized in %)
Ʋ
2. FB
Secondary Value 1 (pressure)
Ʋ
3. FB
Secondary Value 2 (pressure in %)
Current value
Ʋ Non-Ex, Ex-ia and Ex-d instruments
12 mA, ±0.5 mA
Dynamic behaviour output
Dynamic characteristics depending on medium and temperature