10
4 Connection
VEGACONNECT 4 with connection box • Interface converter USB - HART/I²C
32628-EN-170202
4.2 Connection of the sensor/signal conditioning
instrument
VEGACONNECT 4 can be connected to virtually all communication-
capable VEGA instruments. With instruments of the plics
®
series it
can be mounted directly into the sensor. In this case, you can remove
VEGACONNECT 4 out of the connection box and insert it into the
plics
®
device instead of the indicating and adjustment module.
1
2
OPEN
TWIST
USB
LOCK
Fig. 3: Connection possibilities
1 Communication via I²C protocol
2 Communication via HART protocol
Communication via I²C protocol
•
Use of VEGACONNECT 4 in all plics
®
sensors through direct
installation (see connection examples)
•
For connection to the I²C (Com.) interface of older plics
®
sensors,
connection 1
Communication via HART protocol
•
For connection to the 4 … 20 mA cable (the supplied HART
resistor will be required depending on voltage supply/processing),
connection 2
In hazardous Ex areas, the HART or I²C cable of VEGACONNECT 4
can be connected to an Ex approved sensor. VEGACONNECT 4 and
the PC must not be located in Ex area.
VEGACONNECT 4 can be connected to the I²C bus interface of the
following sensors.
•
all sensors of plics
®
series
•
VEGACAP from software version 1.10
•
VEGADIS 81/82
Connection via I²C bus