N
ote
:
S
crew the housing cover tightly to the point where the
inspection glass is above the control lamp
(
LED
).
T
o adjust
VEGACAP
62
,
fi
rst of all remove the housing cover
.
W
ith the potentiometer on the signal conditioning instrument
and the meas
.
range selection switch
(
1
)
on
VEGACAP
62
you
can change the switching point of the probe or adapt the
sensitivity of the probe to the electrical properties of the
product and the conditions in the vessel
.
T
his is necessary so
that the level switch can also reliably detect products e
.
g
.
with
very low or very high dielectric value
.
R
ange
1
:
0
…
20
p
F
R
ange
2
:
0
…
85
p
F
R
ange
3
:
0
…
450
p
F
S
ignal lamp for indication of the device status
.
l
green
=
instrument functions
l
red
(
fl
ashing
)
=
failure
T
he adjustment of the switching point is only possible in
installed condition
.
T
he detailed adjustment of
VEGACAP
62
is described in the
"
O
perating instructions manual of the signal conditioning
instrument
"
.
M
easuring range selection
switch
(
1
)
S
ignal lamp
(
4
)
S
witching point adjustment
VEGACAP
62
-
with two
-
wire output
21
S
et up
30007
-
EN
-
060222