6 Set up with the display and adjustment module PLICSCOM
VEGACAL 62 • Profibus PA
30025-EN-160331
Service
Basic adjustment
4
Display
Diagnostics
▶
Service
Info
Additional PA value
4.1
Secondary Value 1
Out-Scale-Unit
4.2
Volume
hl
PV-Out-Scale Min.
4.3
0 % = 5.0 hl
100 % = 5000.0 hl
Simulation
4.4
Start simulation?
Reset
4.5
Select reset?
Language
4.6
German
Copy sensor data
4.7
Copy sensor data?
PIN
4.8
Enable?
Info
Basic adjustment
5
Display
Diagnostics
Service
▶
Info
Instrument type
5.1
VEGACAL 6x
Serial number
12345678
Date of manufacture
5.2
06. February 2012
Software version
1.30
Last change using PC
5.3
05. March 2012
Sensor characteristics
5.4
Display now?
6.10 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If VEGACAL 62 is equipped with a display and adjustment module,
the most important data can be read out of the sensor into the display
and adjustment module. The procedure is described in the operating
instructions manual "
Display and adjustment module
" in the menu
item "
Copy sensor data
". The data remain there permanently even if
the sensor power supply fails.
If it is necessary to exchange the sensor, the display and adjustment
module is inserted into the replacement instrument and the data are
written into the sensor under the menu item "
Copy sensor data
".