1 Functional safety

VEGACAL series 60 • Two-wire 4 … 20 mA/HART

35593-EN-181129

An associated characteristic is the value PFH (failure rate).
Number values see chapter "

Safety-related characteristics

".

The following assumptions form the basis for the implementation of 

FMEDA:

• 

Failure rates are constant, wear of the mechanical parts is not 

taken into account

• 

Failure rates of external power supplies are not taken into account

• 

Multiple errors are not taken into account

• 

The average ambient temperature during the operating time is 

40 °C (104 °F)

• 

The environmental conditions correspond to an average industrial 

environment

• 

The lifetime of the components is around 8 to 12 years 

(IEC 61508-2, 7.4.7.4, remark 3)

• 

The repair time (exchange of the measuring system) after an non-

dangerous malfunction is eight hours (MTTR = 8 h)

• 

The processing unit can interpret "

fail low

" and "

fail high

" failures 

as a disruption and trigger a suitable error message

• 

The scanning interval of a connected control and processing unit 

is max. 1 hour, in order to react to dangerous, detectable errors

• 

Existing communication interfaces (e. g. HART, I²C-Bus) are not 

used for transmission of safety-relevant information

The measuring system should be used appropriately taking pressure, 

temperature, density, dielectric value and chemical properties of the 

medium into account.
The user-specific limits must be complied with. The specifications of 

the operating instructions manual must not be exceeded.
Keep in mind when using as dry run protection:

• 

Avoid rod or cable breakage (probably smaller proof test intervals 

will be necessary)

1.3  Instrument parameter adjustment

Since plant conditions influence the functional safety of the measur-

ing system, the instrument parameters must be set in compliance with 

the application.
The following tools are allowed:

• 

The DTM suitable for VEGACAL in conjunction with an adjustment 

software according to the FDT/DTM standard, e. g. PACTware

• 

Display and adjustment module

Note:

Make sure that DTM Collection 10/2005 or a newer version is used.

If the measuring system has not been ordered especially for applica-

tions in safety-instrumented systems (SIS), the parameter "

Sensor 

according to SIL

" must be selected in the adjustment sofware in the 

menu level "

Basic setting

". If the display and adjustment module 

Assumptions

General instructions and 

restrictions

Adjustment tools

Create a measurement 

loop

Содержание VEGACAL 60 Series

Страница 1: ...Safety Manual VEGACAL series 60 Two wire 4 20 mA HART Document ID 35593...

Страница 2: ...1 Functional safety 3 1 1 General information 3 1 2 Planning 4 1 3 Instrument parameter adjustment 6 1 4 Setup 7 1 5 Reaction during operation and in case of failure 7 1 6 Recurring function test 8 1...

Страница 3: ...ant architecture is excluded The SIL conformity is confirmed by the verification documents in the appendix SIL Safety Integrity Level HFT Hardware Fault Tolerance SFF Safe Failure Fraction PFDavg Aver...

Страница 4: ...According to IEC 61511 1 paragraph 11 4 4 the failure tolerance HFT can be reduced by one for service proven subsystems if the fol lowing conditions are met The instrument is service proven Only proce...

Страница 5: ...responding portions of the failure rates must be assigned to the dangerous failures The stated values in chapter Safety relevant characteristics can thus worsen The processing unit must correspond to...

Страница 6: ...s e g HART I C Bus are not used for transmission of safety relevant information The measuring system should be used appropriately taking pressure temperature density dielectric value and chemical prop...

Страница 7: ...rized modification the set parameters must be protected against unintentional access Activate the password protection in the adjustment software Activate the PIN on the display and adjustment module A...

Страница 8: ...hitectures it is a good idea to verify the effect of the redundancy through recurring function tests at appropriate intervals Please carry out the test in such a way that the correct safety function i...

Страница 9: ...F MTTF MTTR 0 93 x 106 h E013 no measured value available 10 sek E036 E037 no executable sensor software 1 h Single channel architecture SIL SIL2 HFT 0 Instrument type Type B Applies to overfill and d...

Страница 10: ...years Multiple channel architecture If the measuring system is used in a multiple channel architecture the safety relevant characteristics of the selected structure of the meas chain must be calculat...

Страница 11: ...11 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129 2 Supplement...

Страница 12: ...12 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Страница 13: ...13 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Страница 14: ...14 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Страница 15: ...15 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Страница 16: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Отзывы: