6 Set up with the display and adjustment module PLICSCOM
VEGABAR 66 • 4 … 20 mA/HART - climate compensated
36738-EN-130321
Unit
Unit of measurement
bar
▼
Temperature unit
°C
▼
3.
Activate the selection with
[OK]
and select "
Units of measure-
ment
with
[->]
.
4.
Activate the selection with
[OK]
and select the requested unit with
[->]
(in the example mbar).
5. Confirm with
[OK]
and move to position correction with
[->]
.
The adjustment unit is thus switched over from bar to mbar.
Proceed as follows to select the temperature unit:
6)
1.
Activate the selection with
[OK]
and select "
Temperature unit
with
[->]
.
2.
Activate the selection with
[OK]
and select the requested unit with
[->]
(e.g. °F).
3. Confirm with
[OK]
.
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "
Position correction
" the selection with
[OK]
.
Position correction
Offset
P
=
+0000
mbar
53
mbar
2.
Select with
[->]
, e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3. Confirm with
[OK]
and move to min.(zero) adjustment with
[->]
.
Proceed as follows:
1. Edit the mbar value in the menu item "
zero
" with
[OK]
.
Zero
000.0 %
P
=
+0000.0 mbar
0000.0
mbar
2.
Set the requested mbar value with
[+]
and
[->]
.
3. Confirm with
[+]
and move to span adjustment with
[->]
.
The zero adjustment is finished.
Carry out a position cor-
rection
Carrying out zero adjust-
ment
6)
Selection options: °C, °F.