![Vega VEGABAR 28 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/vega/vegabar-28/vegabar-28_operating-instructions-manual_859551036.webp)
36
10 Diagnostics and servicing
VEGABAR 28 • Three-wire 1 x transistor or 4 … 20 mA
57534-EN-220826
Code
Text message
Cause
Rectification
F013
no measured value available
Hardware error in the area of the meas-
uring cell
Send instrument for repair
F017
Adjustment span too small
Adjustment not within specification
Change adjustment
F036
no operable sensor software
Failed or interrupted software update
Repeat software update
F080
General software error
General software error
Restart
F110
Switching points too close to-
gether
Selected switching points too close to-
gether
Increase the distance between the
switching points
F111
Switching points inter-
changed
Switching point 1 is smaller than switch-
ing point 2
Select switching point 1 to greater than
switching point 2
F260
Error in the calibration
Checksum error in the calibration val-
ues
Send instrument for repair
F261
Error in the instrument set-
tings
Checksum error in the configuration
values
Carry out a reset
Code
Text message
Cause
Rectification
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after
60 mins.
Code
Text message
Cause
Rectification
S600
Impermissible electronics
temperature
Temperature of the electronics in the
non-specified range
Check ambient temperature
Insulate electronics
S604
Switching output overloaded
Overload or short circuit at output 1 or 2 Electrical connection, check load re-
sistance
Code
Text message
Cause
Rectification
M504
Error at a device interface
Interference of the internal communica-
tion to Bluetooth
Restart
Send instrument for repair
Failure
Function check
Out of specification
Maintenance