5
C
onnecting to power supply
5
.
1
P
reparing the connection
A
lways keep in mind the following safety instructions
:
l
C
onnect only in the complete absence of line voltage
l
I
f overvoltage surges are expected
,
overvoltage arresters should
be installed
T
ip
:
W
e recommend
VEGA
overvoltage arrester Ü
SB
62
-
36
G
.
X
.
I
n hazardous areas you must take note of the respective regulations
,
conformity and type approval certi
fi
cates of the sensors and power
supply units
.
T
he supply voltage and the current signal are carried on the same two
-
wire connection cable
.
P
rovide a reliable separation between the supply circuit and the mains
circuits according to
DIN VDE
0106
part
101
.
VEGA
power supply units
VEGATRENN
149
AE
x
,
VEGASTAB
690
,
VEGADIS
371
as well as all
VEGAMET
s meet this requirement
.
W
hen
using one of these instruments
,
protection class
III
is ensured for
VEGABAR
17
.
K
eep in mind the following additional factors that in
fl
uence the
operating voltage
:
l
O
utput voltage of the power supply unit can be lower under
nominal load
(
with a sensor current of
20
.
5
m
A
or
22
m
A
in case of
fault message
)
l
I
n
fl
uence of additional instruments in the circuit
(
see load values in
chapter
"
T
echnical data
"
)
T
he instrument is connected with standard two
-
wire cable without
screen
.
I
f electromagnetic interference is expected which is above the
test values of
EN
61326
for industrial areas
,
screened cable should be
used
.
U
se cable with round cross
-
section
.
A
cable outer diameter of
5
…
9
mm
(
0
.
2
…
0
.
35
in
)
ensures the seal e
ff
ect of the cable gland
.
I
f you are
using cable with a di
ff
erent diameter or cross
-
section
,
exchange the
seal or use a suitable cable gland
.
F
or the version with round plug connector
M
12
x
1
,
a suitable
,
ready
-
made connection cable
(
article no
.
ASL
.
1
S
.)
in
5
m
,
10
m or
25
m
lengths is available from the line of
VEGA
accessories
.
N
ote safety instructions
T
ake note of sa
-
fety instructions
for
E
x applica
-
tions
S
elect power supply
S
elect connection cable
12
VEGABAR
17
5
C
onnecting to power supply
27636
-
EN
-
120531
Содержание VEGABAR 17
Страница 1: ...Operating Instructions VEGABAR 17 Document ID 27636 Process pressure ...
Страница 11: ...Fig 2 Mounting of VEGABAR 17 VEGABAR 17 11 4 Mounting 27636 EN 120531 ...
Страница 34: ...34 VEGABAR 17 9 Supplement 27636 EN 120531 ...
Страница 35: ...VEGABAR 17 35 9 Supplement 27636 EN 120531 ...