![Vega PLICSMOBILE T81 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/vega/plicsmobile-t81/plicsmobile-t81_operating-instructions-manual_3821028023.webp)
23
6 Battery operation and power saving mode
PLICSMOBILE T81/B81/S81 • External GSM/GPRS/UMTS radio unit
55234-EN-170206
Operating times with PLICSMOBILE B81
In the following table you can find exemplary the operating times
when using PLICSMOBILE B81, depending on the number of
sensors and messages per day as well as activated/deactivated
Bluetooth function.
Number of mes-
sages
Number of sen-
sors
Operating time
of the battery in
years
Operating time
of the accumula-
tor in years
1
1
>10/3.7*
3/0.7*
5
5.1/2.5*
0.9/0.5*
10
2.9/1.8*
0.3/0.3*
24
1.3/1.0*
0.2/0.2*
1
2
>10
2.8
5
4.6
0.9
10
2.6
0.5
24
1.1
0.2
1
5
>10
2.4
5
3.6
0.7
10
1.9
0.4
24
0.9
0.2
The values marked with * correspond to the operating time with acti-
vated Bluetooth module.
6.5 Power options
In the DTM (see chapter "
Parameter adjustment with PACTware"
)
you can select under the menu item "
Energy options
" between the
modes "
Continuous operation
" and "
Power saving mode
".
In continuous (non-stop) operation PLICSMOBILE and the sensor
always remain switched on. Only in this mode can the instrument be
used for level monitoring and send an e-mail when a certain level is
reached or when an error occurs (measured value/status-controlled
transmission). In continuous operation PLICSMOBILE allows remote
parameter adjustment via the service department. Configuration
changes on PLICSMOBILE as well as the sensor can thus be carried
out remotely from any PC with PACTware via GPRS.
In this mode, the integrated GSM modem as well as the sensor
connected to PLICSMOBILE are switched on automatically when
the time-controlled transmission of a message is pending. After the
measured value is recorded, the log-in into the GSM network is car-
ried out and the measured value is transmitted. The instrument then
returns to power saving mode. The time for this process depends on
the network quality and is generally approx. 70 seconds.
Permanent operation
Power saving mode