Vega SI-21 / User Manual
Revision 11 – 23 October 2020
29
16
Communication period
1 byte
1 – 1 hour
2 – 6 hours
3 – 12 hours
4 – 24 hours
5 – 5 minutes
6 – 15 minutes
7 – 30 minutes
49
Data collection period
1 byte
1 – 1 hour
2 – 6 hours
3 – 12 hours
4 – 24 hours
5 – 5 minutes
6 – 15 minutes
7 – 30 minutes
55
Time zone, in minutes
2 bytes
from -720 to 840
78
Data collection period when
temperature is out of the thresholds
1 byte
1 – 1 hour
2 – 6 hours
3 – 12 hours
4 – 24 hours
5 – 5 minutes
6 – 15 minutes
7 – 30 minutes
79
Immediately send data when
temperature is out of range
1 byte
0 – OFF
1 – ON
80
Low temperature threshold
1 byte
from -128 to +127
81
High temperature threshold
1 byte
from -128 to +127