background image

 

 

Vega SI-11 / User Manual  

 

 

Revision 25 -  24 June 2021 

 

DEFAULT DEVICE SETTINGS 

 

PARAMETER 

VALUE 

Frequency plan 

RU868 

Activation type 

OTAA 

Adaptive Data Rate 

ON 

Confirmed Uplinks 

OFF 

Rx 1 Delay 

1 second 

Join Accept Delay 

5 seconds 

Uplink number of transmissions 

Data rate 

DR0 

Power  

14 dBm 

Communication period 

24 hours 

Data collection period  

24 hours 

Time zone 

UTC +00:00 

Inputs operate in mode 

pulse 

For changing the device settings,  you need to connect to it with “Vega  LoRaWAN 

Configurator” application. You can download app on the iotvega.com site in SOFT section as 
well as User Manual for configurator

Go to the app page

  

 

Содержание VEGA SI-11

Страница 1: ...www vega absolute ru PULSE COUNTER VEGA SI 11 USER MANUAL DOCUMENT REVISION FIRMWARE VERSION 25 2 4...

Страница 2: ...7 Device Specification 7 Default Device Settings 8 3 OPERATION 9 Device Appearance 9 Contacts Description 10 LED Indications 12 Mounting Recomendations 13 4 COMMUNICATION PROTOCOL 15 Vega SI 11 pulse...

Страница 3: ...ion on powering and activation procedure control commands and functions of the counter This manual is targeted at specialists familiar with installation work fundamentals of electronic and electrical...

Страница 4: ...UNICATION AND DATA COLLECTION ALGORITHM Vega SI 11 operates in modes listed below Storage is a mode for storing and transporting In this mode the device does not communicate regularly with the network...

Страница 5: ...receiving a confirmation of the delivery of the previous one If such confirmation has not been received after the fulfilled in the settings uplink number of transmissions device completes the communi...

Страница 6: ...battery MARKING Device marked with sticker that contain the next information Device name DevEUI Release Date Sticker located in three places on device case in factory certificate and on the packing b...

Страница 7: ...on type ABP or OTAA Communication period 5 15 30 minutes 1 6 12 or 24 hours Data collection period 5 15 30 minutes 1 6 12 or 24 hours Memory amount for storing packets 200 packets Type of the LoRaWAN...

Страница 8: ...Delay 5 seconds Uplink number of transmissions 1 Data rate DR0 Power 14 dBm Communication period 24 hours Data collection period 24 hours Time zone UTC 00 00 Inputs operate in mode pulse For changing...

Страница 9: ...unting for DIN rail 1 screw 2 mm 8 mm cross 2 DIN rail with mounting holes 3 mm 3 silicone gasket without through holes ensuring the protection rating of the device case IP65 All of elements for manag...

Страница 10: ...tacts reed switch mechanical pushbutton open collector output Equipment with NAMUR pulse output is not supported Polarity effects only open collector circuits To reset all readings from the pulse inpu...

Страница 11: ...Vega SI 11 User Manual 11 Revision 25 24 June 2021 The maximum possible frequency of sending alarm packets is one per 1 second...

Страница 12: ...ING Short flashings Linking to the network in progress One long flashing during 5 sec The device has been successfully connected to the network and is in active mode Three flashings each by 1 sec Link...

Страница 13: ...ng be like 1 Setting the devices and connecting them to the network are usually carried out in the office see Network Deployment Manual 2 Determination of suitable places for mounting at the object wi...

Страница 14: ...ice it is necessary to reset the pulses accumulated during testing and connection by switching the device to the Storage mode by pressing the button for 5 seconds 9 Start the device by pressing launch...

Страница 15: ...on the type number of pulses or status 0 open 1 closed uint32 4 bytes Input 2 reading depending on the type number of pulses or status 0 open 1 closed uint32 4 bytes Input 3 reading depending on the...

Страница 16: ...e Values of basic settings bit field uint8 1 byte Input No where the alarm is detected uint8 4 bytes Packet time unixtime UTC uint32 4 bytes Input 1 reading depending on the type number of pulses or s...

Страница 17: ...ed to the network Size in bytes Field description Data type 1 byte Packet type this packet 0 uint8 2 bytes ID of parameter uint16 1 byte Data length len uint8 len bytes Parameter value 2 bytes ID of p...

Страница 18: ...ical to such packet from device Size in bytes Field description Data type 1 byte Packet type this packet 0 uint8 2 bytes ID of parameter uint16 1 byte Data length len uint8 len bytes Parameter value 2...

Страница 19: ...4 mode 1 byte 1 pulse 2 guard 16 Communication period 1 byte 1 1 hour 2 6 hours 3 12 hours 4 24 hours 5 5 minutes 6 15 minutes 7 30 minutes 49 Data collection period 1 byte 1 1 hour 2 6 hours 3 12 hou...

Страница 20: ...N REQUIREMENTS Vega SI 11 pulse counter shall be stored in the original packaging in heated room at temperatures 5 to 40 and relative humidity less than 85 The counter shall be transported in covered...

Страница 21: ...Vega SI 11 User Manual 21 Revision 25 24 June 2021 6 CONTENT OF THE PACKAGE The pulse counter is delivered complete with Vega SI 11 pulse counter 1 pc Screw 4 pcs Factory certificate 1 pc...

Страница 22: ...t have a factory certificate the factory certificate does not have an TCD stamp and or there is no sticker with information about the device the serial number DevEUI EMEI printed on the product differ...

Страница 23: ...P Fixed error in protocol description 13 16 08 2017 PKP Adding s in alarm command description 14 08 09 2017 KEV Part Vega LoRaWAN Configurator was added 15 11 10 2017 KEV Warranty was changed minor ed...

Страница 24: ...1 23 08 04 2020 KEV Fixed inaccuracy about data type in Temperature field minor changes 24 09 06 2020 KEV The battery information is changed in the specification 25 24 06 2021 KEV Scheduled revision o...

Страница 25: ...Vega SI 11 User Manual 25 Revision 25 24 June 2021 vega absolute ru User Manual Vega Absolute OOO 2017 2021...

Отзывы: