![Veesta World V-PM1000 Series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/veesta-world/v-pm1000-series/v-pm1000-series_user-manual_859430017.webp)
VP-1405A Advanced Power
Chapter 3 - Specifications
V-PM1000 Series, Veesta Power Module Product Series
48V Power Supply & Charger Instructions & User's Manual
Page 17 of 46
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
3.1.6
General Specifications
1.
Efficiency
:
84% in typical AC input, 5A output, full battery
2.
Temperature Coefficient :
± 0.02 % per degree of centigrade (ºC)
In typical input voltage, 5A output
3.
Indicators
:
6 LEDs
4 Keys
4.
Insulation Resistance
:
(Test Voltage 500 VDC)
Input to Output: 80 MΩ
Input to Case: 80 MΩ
Output to Case: 80 MΩ
5.
Isolation Voltage
:
Input to Output: 2250 VAC / 5mA / 1 min
Input to Case: 2250 VAC / 5mA / 1 min
Output to Case: 500 VDC / 5mA / 1 min
Alarm contact to coil: 3000 VAC / 5mA / 1 min
RS485 port to system: 2500 VAC / 5mA / 1 min
3.1.7
Environment
1.
Operating Condition
:
Temperature range: -25 to +60°C
Ambient temperature over +55°C should position
module heat sink in air cooled position that case
temperature should not exceed of +85°C
2.
Storage Condition
:
Temperature range: -40 to +100°C
3.
Humidity Condition
:
RH: 5-90% non-condensed
3.1.8
Dimension / Physical
1.
Dimension
:
Width: 170mm
Length: 120mm
Height: 45mm
2.
Mounting
:
Wall mount with flange holders
3.
Weight
:
Approx. 1.4 kg.