![Veesta World V-PM1000 Series Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/veesta-world/v-pm1000-series/v-pm1000-series_user-manual_859430016.webp)
VP-1405A Advanced Power
Chapter 3 - Specifications
V-PM1000 Series, Veesta Power Module Product Series
48V Power Supply & Charger Instructions & User's Manual
Page 16 of 46
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization.
3.1.4
Communication Port
1.
Rear Panel port
:
RS-485 Network 2 wires for networking to master
Baud-rate: 2400, 9600, 19200, 38400 bps
Parity: None, Odd, Even
Start/Stop: 1 bit, 2 bits
2.
Port Specifications
:
RJ-45 Connection Port
Isolated 2500V communication port
3.
Communication Protocol :
ModBus RTU Protocol
Slave Address: 1~247
Function Support: 03/04/06/16
Factory Defaults: 9600 bps
4.
Factory Defaults
:
Baud rate: 9600 bps
Parity: None
Start/Stop: 1 bit
Slave Address ID: 200
3.1.5
Alarm outputs
1.
Relay Outputs
:
4x Configurable Alarm Output Relays
Default Alarms:
- Alarm Out 1: AC Input Power OK Status
- Alarm Out 2: Any Failure Alarm
- Alarm Out 3: Battery Fail/Under voltage Alarm
- Alarm Out 4: Battery Disconnect Alarm
2.
Contact Switching Current :
1.0 A
3.
Contact Rating Voltage
:
250 VAC
4.
Contact / Coil Isolation
:
Voltage
3 kV
5.
Contact Short Circuit
:
Protection
Activate on maximum 1.1 A
Auto-resettable Fuse