System Setup Screens

[201-203, 240] System Language and Units Setup Screen

9

[201-203, 240] System Language and Units Setup Screen

 

Legend for numbered boxes 

01-01-2000

12:00 AM

ALL FUNCTIONS NORMAL

3

4

2

1

[201]

[202]

[203]

[240]

ISO 3166 COUNTRY

1

System Language [201] - Choose from English, 
(default), French, Spanish, German, Portuguese, Polish, 
Swedish, Finnish, Russian or Chinese (Mandarin).

2

Units [202] - Choose Metric (default) or U.S.

3

Serial Language [203] -Choose from English (default), 
French, Spanish, German, Portuguese, Polish, Swedish, 
Finnish or Russian.

4

ISO Country Code [240] - This feature is an 
international option. Enter the three alpha-character 
country code. Default is blank.

Содержание TLS2P

Страница 1: ...Manual No 577013 960 Revision D Software Version 5 Setup and Operation Manual TLS2P Console Ethernet USB 3 COMS...

Страница 2: ...r Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Страница 3: ...reen 20 238 239 COMM Ports 1 2 3 Serial Setup Screen Page 1 21 238 Comm Type Selection Dialog 22 249 252 COMM Ports 1 2 3 Setup Screen Page 2 23 238 239 241 253 COMM Port 1 Printer Setup Screen 24 238...

Страница 4: ...Shift Close Screen 61 Manually Starting Stopping Tank Leak Tests 112 114 129 130 Manual Test Start Stop Screen 62 Reports System Reports 63 Inventory Report US Units and Non Density Probe 65 Inventory...

Страница 5: ...ox 81 Figure 5 TLS2P Web Server Home Page 83 Figure 6 TLS2P Web Server Inventory Page 84 Figure 7 TLS2P Web Server Delivery Page 85 Figure 8 TLS2P Web Server Alarms Page 86 Tables Table 1 Alarm Messag...

Страница 6: ...minimum training certifications for contractors who will install and setup the equipment discussed in this manual Installer Level 1 Certification Contractors holding valid Installer Certification are...

Страница 7: ...e tanks FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY ENVIRONMENT RESULTING IN SERIOUS INJURY OR DEATH Leaking tanks can create serious environmen...

Страница 8: ...Testing Method standards and has been third party tested by Midwest Research Institute This system can detect a 0 1 gph leak exceeding a 95 probability of detection P D and less than a 1 probability...

Страница 9: ...Remove water from the tank Invalid Fuel Height Tank Fuel level dropped to a point below the minimum detectable level or only one float is present Call for delivery Low Product Tank Tank level dropped...

Страница 10: ...button touch to acknowledge alarm and silence alarm beeper Note touching this button does not clear the alarm the problem that caused the alarm must be repaired 4 Print button For menu screens touch...

Страница 11: ...l Test button touch to display the Manual Tank Test Start Stop Screen page 62 3 Function Test button touch to display the Function Test Menu Screen page 72 4 Tank Setup button touch to display the Tan...

Страница 12: ...word Screen will not display Legend for numbered boxes 01 01 2010 12 00 AM ALL FUNCTIONS NORMAL 1 266 SYSTEM SETUP ENTER PASSWORD PASSWORD 1 Password 266 To access the System Setup Screen page 8 you m...

Страница 13: ...play the Station Header Setup Screen page 10 6 Shift Time button touch to display the Setup Shift Times Screen page 19 7 Dialing Setup button touch to display the System Setup Dial Out Setup Screen pa...

Страница 14: ...COUNTRY 1 System Language 201 Choose from English default French Spanish German Portuguese Polish Swedish Finnish Russian or Chinese Mandarin 2 Units 202 Choose Metric default or U S 3 Serial Language...

Страница 15: ...d the Roman alphabet are supported 2 Header Line 2 205 Enter second line of Report header The entry can be alphanumeric and up to 20 characters Only numbers and the Roman alphabet are supported 3 Head...

Страница 16: ...entered window 2 4 Save button touch to accept entered data and close Screen 5 Cancel button touch to cancel any entry and close Screen 6 Cursor left button touch to move the cursor one position left...

Страница 17: ...ata Entered Window 2 4 Save button touch to accept entered data and close Screen 5 Cancel button touch to cancel any entry and close Screen 6 Cursor left button touch to move the cursor one position l...

Страница 18: ...ty 208 Select Security Enabled or Disabled for the selected COMM port default is Disabled If COMM port 1 is setup for a printer the security code requirement is ignored 2 Password 209 Enter a six digi...

Страница 19: ...e not case sensitive Once you OK the Setup Password you will be required to enter this password before accessing System Setups page 7 and Tank Setups page 46 1 Old Password 263 If you want to change t...

Страница 20: ...2 1 212 213 214 TM DATE FORMAT DD MM YY HH MM 10 04 01 13 54 1 Date 212 Enter current date 2 Time 213 Enter current time 3 TM Date Format 214 Select one of 3 formats DD MM YY HH1 MM default YY MM DD H...

Страница 21: ...ry Screen 16 Current Date Entry Screen Legend for numbered boxes 1 6 2 3 2001 1 Month entry window enter 01 12 2 Day entry window enter 01 31 3 Year entry window enter year e g 2001 The remaining butt...

Страница 22: ...y window enter 00 23 or 01 121 2 Minutes entry window enter 01 59 3 AM PM entry window1 enter AM or PM 4 Touch PM if after noon1 5 Touch AM if before noon1 The remaining buttons function as described...

Страница 23: ...d for the remaining tanks the shift number increments and a shift report is created If the system is setup to autodial on Shift Close Event the autodial assigned receiver will be sent the notification...

Страница 24: ...for all shifts NOTE At least one shift start time must be entered to activate the Last Shift Inventory feature 1 Shift 1 215 touch the time button to the right of the window and enter the Shift 1 star...

Страница 25: ...and times you enter 1 Daylight Savings 219 touch the Arrow button to the right of the window and select Enable or Disable default is Disable 2 Start Date 220 touch the Date button to the right of the...

Страница 26: ...Printer COMM 2 selections None Serial COMM 3 selections None Serial 2 Handshaking 239 touch the Down Arrow button to the right of the window and select COMM 1 Hardware XON XOFF None COMM 2 and 3 XON...

Страница 27: ...tiple options so you touch the arrow button to select an option 1 Comm Type 238 touch the Down Arrow button to the right of the window and to select a different Comm Type for the following COMM Ports...

Страница 28: ...Down Arrow button to the right of the window and select a desired baud rate 300 600 1200 2400 4800 or 9600 default 2 Parity 250 touch the Down Arrow button to the right of the window and select a pari...

Страница 29: ...e right of the window and select Yes or No default If the page eject is set to Yes a page feed command will be sent to the printer at the conclusion of the report or when a report exceeds the length o...

Страница 30: ...up button touch the Advanced Setup button and go to the Advanced Communications Setup Screen page 26 2 Modem Type 244 touch the Down Arrow button to the right of the window and select your external mo...

Страница 31: ...1 SYSTEM SETUP COMMUNICATIONS COMM 1 247 248 DIAL IN AT B1 AT B1 CAUTION Entering the wrong number strings in this screen may disable the modem 1 Dial In 247 touch the Numeric Keypad button and enter...

Страница 32: ...an cause the console to stop functioning Host Port should be set from 10001 to 10010 in order for the Web Interface to work 6 Remote IP address which is the address that the console will connect to if...

Страница 33: ...ees the TLS2P from having to be in continual commuication with the Lantronix server 1 Current Host IP 280 Address in Lantronix server 2 Current Subnet Mask Address 281 in Lantronix server 3 Current Ga...

Страница 34: ...s for these fields must fall within the range of 0 255 to be accepted 2 Right Left arrows touch to select the desired field 3 Save button touch to accept entered data and close screen 4 Cancel button...

Страница 35: ...ialog box upper screen displays when you touch the GET button on the TCPIP setup screen see page 28 1 OK button touch to have the TLS2P get the TCPIP parameters 280 283 saved in the Lantronix server T...

Страница 36: ...ch the SET button on the TCPIP setup screen see page 28 1 OK button touch to have the TLS2P save the TCPIP parameters 280 283 to the Lantronix server The lower screen displays while the TLS2P is updat...

Страница 37: ...ammable To communicate through the USB port on the console you will need a standard USB printer cable as well as a USB driver for your computer or laptop for the interface to the console The driver th...

Страница 38: ...o Dialout System Setup Dial Out Screen Legend for numbered boxes 05 29 2008 12 00 AM ALL FUNCTIONS NORMAL SYSTEM SETUP DIAL OUT DIAL TYPE 1 270 NONE 1 Dial Type 270 touch the Arrow button to display t...

Страница 39: ...xes SELECT ENTRY DIAL TYPE 1 2 3 270 NONE SAVE CANCEL 1 Dial Type 270 touch the Arrow button to display the Dial Type Select Entry Diaglog and select a Dial Type None default Modem TCPIP EMail 2 Save...

Страница 40: ...one phone number to which you want the system to dial 3 Retries 225 touch the Numeric button to the right of the window and enter the number of times 1 99 you want the system to redial the phone numbe...

Страница 41: ...te IP Address 271 in Lantronix server 3 Current Remote port 272 in Lantronix server 4 Push Site ID 277 This feature will allow the TLS2P to automatically establish a TCPIP connection to a Polling Serv...

Страница 42: ...er 41 characters max Touch alfpha key button to enter edit email address 3 Recipient 2 Email Address 274 in Lantronix server 41 characters max Touch alfpha key button to enter edit email address 4 Fro...

Страница 43: ...ditions Note Autodial alarms continue on next two pages 1 Max Product 227 touch the Down Arrow button to select On dial out or Off do not dial out 2 Overfill Limit 228 touch the Down Arrow button to s...

Страница 44: ...ARMS 231 232 233 234 1 2 3 4 5 6 This screen continues Autodial Alarms setup Note Autodial alarms continue on next page 1 High Water 231 touch the Down Arrow button to select On dial out or Off do not...

Страница 45: ...the Down Arrow button to select On dial out or Off do not dial out 2 Probe Out 236 touch the Down Arrow button to select On or Off 3 Low Temperature 237 touch the Down Arrow button to select On or Of...

Страница 46: ...screen concludes Autodial Alarms Setup 1 Shift Close Event 550 touch the Down Arrow button to select On or Off 2 Density Warning 551 touch the Down Arrow button to select On or Off When set to On you...

Страница 47: ...beeper relay 1 Alarm Relay 256 touch the Down Arrow button to the right of the window and select None default Overfill or All Alarms If Overfill is selected an overfill condition on any tank will acti...

Страница 48: ...e Compensation reference temperature The allowable range is 49 to 120 F 45 to 48 9 C The default is 59 F 15 C 2 Print TC Volume 258 touch the Down Arrow button to the right of the window and select Ye...

Страница 49: ...t Height default or Volume for H Protocol 2 Euro Protocol Prefix 260 Touch the Down Arrow button to the right of the window and select S default or d 3 Stick Height Offset 261 Touch the Down Arrow but...

Страница 50: ...s installed software and features System Software Revision Level Software Part Number Software Creation Date System Features e g Static Tank Leak Detect 06 03 2008 10 57 AM ALL FUNCTIONS NORMAL SOFTWA...

Страница 51: ...isplay Legend for numbered boxes 01 01 2010 12 00 AM ALL FUNCTIONS NORMAL 1 267 TANK SETUP ENTER PASSWORD PASSWORD 1 Password 267 To access the Tank Setup Menu Screen page 47 you must enter the 6 to 1...

Страница 52: ...AM ALL FUNCTIONS NORMAL 2 3 1 This screen contains access to Tank Setup Screens 1 Tank Setup button touch to display the Tank Setup Screen page 48 2 Tank Alarm Limit button Touch to display the Tank...

Страница 53: ...t of the window and select Enabled or Disabled default 2 Prod Label 120 Touch the Down Arrow button to the right of the window and enter up to a 20 character label Only numerals from 0 9 and Roman alp...

Страница 54: ...1 point for flat ended steel tanks default 4 points for fiberglass tanks or 20 points for all tanks 4 Tank Chart button This button only appears if you have selected the 4 point or 20 point Tank Prof...

Страница 55: ...if the probe is located in the center of the tank If the probe is located in the center of the tank the value entered is 000 00 U S units or 0000 0 Metric units If the probe is not in the center of th...

Страница 56: ...085 Gasohol 0 00069 0 00125 Gear Oil 90W 0 00047 0 00085 Hydraulic Oil 0 00047 0 00085 Jet Fuel 0 00047 0 00085 Kerosene fuel oil 1 0 00050 0 00090 LPG Butane 0 00109 0 00196 LPG Propane 0 00160 0 002...

Страница 57: ...use Metric Units between the probe and fill risers Record the measurement in column D 5 Divide the value in column C by column D to determine the pitch Record the results in column E 6 Measure the di...

Страница 58: ...the factory during calibration of the magnets used in the float As the density float can be shipped separately from the probe the user will need to record the Density Code on each density float and t...

Страница 59: ...threshold is referenced to the Full Volume capacity Allowable range is 0 to 100 Default is 0 disabled An active Probe Low Temperature Warning will disable this alarm 3 Delivery Needed 103 Delivery Nee...

Страница 60: ...rtment drops to one tank The feature also allows fuel to settle out after a delivery which is especially important in manifolded tank groups Allowable delay is 1 to 60 minutes Default is 1 Touch the D...

Страница 61: ...Periodic Test Fail 110 Periodic Test Fail allows you to disable or enable an alarm that triggers if a 0 2 gph 0 76 lph leak test fails Choices are Alarm Enabled or Disabled Default is Disabled Touch t...

Страница 62: ...FUNCTIONS NORMAL 1 109 553 DENSITY LOW LIMIT 674 00 KGM3 This screen concludes Tank Alarm Limits setup 1 Density Low Limit 553 touch the numeric button to enter a low limit at which you want the set t...

Страница 63: ...1 gph 0 38 lph requires a Mag 1 probe Touch the Down Arrow button to the right of the window and enter the desired choice 2 Early Stop 113 Disabled is the default setting When enabled this feature wi...

Страница 64: ...nk 1 setup selections on the Tank Leak Test Setup screens to all configured tanks in the system Select No not to transfer the Tank 1 setup to all tanks Default is No If necessary touch the arrow butto...

Страница 65: ...This screen concludes Tank Leak Test Setup 1 Frequency 116 You can choose from several Tank Leak Test frequency options On Date Annually Monthly Weekly Daily Touch the Down Arrow button to the right o...

Страница 66: ...17508 1229 25 500 OK CANCEL 3 4 1 You can manually close the shift for any tank by touching the desired tank s graphic on the screen or 2 You can manually close the shift for all tanks by touching th...

Страница 67: ...button to the right of the window and enter the desired choice 3 Test Rate 112 Select a leak test rate of 0 2 gph 0 76 lph default or 0 1 gph 0 38 lph The 0 1 gph 0 38 lph rate requires a Mag 1 Probe...

Страница 68: ...r HOURLY INVENTORY REPORT Date Hour Volume Height Water Temp See example on page 66 Touch to display Delivery Reports for each tank Includes last delivery and up to previous 9 deliver ies You can touc...

Страница 69: ...e Fullest Pass button to display the results of the last 12 Periodic 1 for each month tests and Last Annual test in which the tank had the most vol ume You can touch the Print button on the display to...

Страница 70: ...3 2 5329 5413 4500 48 8 0 0 37 3 EXAMPLE REPORT PRINTOUT SHIFT INVENTORY REPORT WITH TC VOLUME T 1 REGULAR UNLEADED TANK PRODUCT 1 REGULAR UNLEADED VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP SHIFT 1 S...

Страница 71: ...splayed in the Product box item 2 in the screen above If Temperature Compensated Density is enabled TC will follow the density value e g 769 1 kg m3 TC The other values are in the same locations as fo...

Страница 72: ...Tanker button at the bottom of the screen to view a delivery for that tank EXAMPLE PRINTOUT DELIVERY REPORT WITH NON DENSITY PROBE T 1 REGULAR UNLEADED INCREASE DATE TIME VOLUME TC VOLUME WATER TEMP...

Страница 73: ...delivery for that tank Note If TC Density is enabled then TC Density will be displayed instead of Density EXAMPLE PRINTOUT DELIVERY REPORT WITH DENSITY PROBE T 1 REGULAR UNLEADED INCREASE DATE TIME V...

Страница 74: ...LARM REPORT Date Time of the following last 3 inventory alarms Max Product Overfill Limit Invalid Fuel Level High Water Delivery Needed Low Product and Low Temperature Touch to display the Environment...

Страница 75: ...rm is automatically cleared To clear a failed leak test alarm a passing leak test must be run In Tank Alarm Information MAX PRODUCT ALARM If the product level volume exceeds the Max Product value the...

Страница 76: ...disable the alarm HIGH WATER ALARM If the water level height continuously exceeds the High Water threshold for a period exceeding 3 minutes the High Water Warning will activate The high water alarm w...

Страница 77: ...inter button Touch and a test line will print to a connected printer 4 RED LED button Touch and the red front panel LED turns On for several seconds 5 GREEN LED button Touch and the green front panel...

Страница 78: ...return to the Function Test Menu Screen Probe Diagnostic Screen Touch the down arrow to view available probe temperature data To view another tank s probe diagnostics touch the desired tank s Diagnost...

Страница 79: ...ve water measurement capability it will inhibit water related data TANK 1 2 3 PROBE TYPE MAG 1 MAG 1 MAG 1 SERIAL NUMBER 168809 50069 50069 PROBE ID 0XC000 0XC000 0XC000 PROBE LENGTH 30 00 18 0 18 0 G...

Страница 80: ...2 Overfill page 72 103 Delivery Needed page 72 104 Low Product page 72 105 High Water page 55 106 Delivery Delay page 55 107 Ann Leak Test Min page 55 108 Per Leak Test Min page 55 109 Gross Test Fail...

Страница 81: ...tem Language page 9 202 Units page 9 203 Serial Language page 9 204 Header 1 page 10 205 Header 2 page 10 206 Header 3 page 10 207 Header 4 page 10 208 Security page 13 209 Password page 13 212 Date p...

Страница 82: ...Annual Test Fail page 39 235 Invalid Fuel Height page 40 236 Probe Out page 40 237 Low Temperature page 40 238 Comm Type page 21 page 22 page 24 page 25 239 Handshaking page 21 page 24 240 ISO 3166 C...

Страница 83: ...6 Password page 7 267 Password page 46 270 Dial Type page 33 page 35 page 36 page 37 271 Remote IP page 36 272 Remote Port page 36 273 Recipient 1 page 37 274 Recipient 2 page 37 275 From page 37 276...

Страница 84: ...ndex Probe Diagnostic Screen 79 550 Shift Close Event page 41 551 Density Warning page 41 552 Density High Limit page 56 553 Density Low Limit page 57 Table 7 System Setup Label Codes Label Code Label...

Страница 85: ...nd click the go to button You should see the TLS2P Home screen Connecting a Laptop Directly to the TLS2P What You Will Need Ethernet crossover cable IP address of TLS2P A Static IP address for laptop...

Страница 86: ...Connection Properties screen displays Figure 3 Figure 3 Local Area Connection Properties Screen 4 In the connections or components used check list window highlight Internet Protocol TCP IP and then cl...

Страница 87: ...your browser and enter the IP Address of the TLS2P and click the Go To button You should see the TLS2P Web Server Home Page TLS2P Web Server Main Pages Home Page Displays after connecting to TLS2P web...

Страница 88: ...Accessing The TLS2P Web Server Probe Diagnostic Screen 83 Figure 5 TLS2P Web Server Home Page...

Страница 89: ...Accessing The TLS2P Web Server Probe Diagnostic Screen 84 Figure 6 TLS2P Web Server Inventory Page...

Страница 90: ...Accessing The TLS2P Web Server Probe Diagnostic Screen 85 Figure 7 TLS2P Web Server Delivery Page...

Страница 91: ...Accessing The TLS2P Web Server Probe Diagnostic Screen 86 Figure 8 TLS2P Web Server Alarms Page...

Страница 92: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: