Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF)
Connecting Probes to the TLS-IB
4-2
Connecting Probes to the TLS-IB
Connect the two color-coded/marked wires from each probe to the appropriate connectors (e.g., Probe 1) of the
Probe Terminal Block as shown in Figure 4-1.
Observe polarity when connecting probe wires!
Connect probe cable shields and drain wires to ground in the TLS-IB only, not at the field junction boxes. Do not
ground both ends of the shield.
AUTO PROBE CONFIGURATION
During a cold boot, the TLS-IB will automatically configure connected probes -
CAUTION! For auto
configuration to occur, probes must be connected in sequence, starting at the Probe 1 input and
continuing with no skipped inputs.
For example, if you have 4 probes and you connect them to Probe inputs 1, 2, 3, and 4, auto configuration works
fine. But if you connect them to Probe 1, 3, 5, and 7 auto configuration doesn’t work, resulting in probe out alarms.
Also, the skipped inputs will be unusable.
MANUAL PROBE CONFIGURATION
If you connect probes after the system has been powered they must be manually configured. To configure probes
for the TLS-IB, use either the IFSF command Data ID 1, “Nb-Tanks” (see Table 4-4 on page 4-16); or the RS-232
“Set Tank Configuration”, serial command 601 (see Table 4-3 on page 4-15).