Wiring Instructions

Enclosure Grounding

8

Figure 5.   Overfill Alarm Ground Wire Termination

Table 1.   Console Connections

Input

TLS2 or TLS-

IB

Connection

TLS-50 or 

TLS-HLD

Connection

TLS-300

Output Relay

Connection

TLS-350

I/O Combo 

Relay

Connection

TLS-350

4 Relay Output 

Module

Connection

TLS-4XX

Overfill Alarm 

Relay Connector

Overfill Alarm without Acknowledge Switch (see Figure

 

4)

Overfill Alarm terminal 2 

J6, 1

J5, 1

NO

NO

NO

NO

Line (from power panel)

J6, 2

J5, 2

C

C

C

C

Overfill Alarm with Acknowledge Switch (see Figure

 

3)

Ack Switch terminal 1

J6, 1

J5, 1

NO

NO

NO

NO

Ack Switch terminal 5 (line)

J6, 2

J5, 2

C

C

C

C

Star Washer
(against enclosure) 

Ground Wire

KEPS Nut

Содержание Overfill Alarm

Страница 1: ...Installation Guide OverfillAlarm Manual No 576013 589 Revision F...

Страница 2: ...r Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Contact Veeder Root Customer Service at 800 873 3313 with the specific part numbers and quantities that were missing or received damaged 2 Fax...

Страница 3: ...Overfill Alarm Horn Delay Time 9 Testing the Overfill Alarm with the Acknowledgment Switch 9 Setting the Overfill Alarm Horn s Volume Level 9 Testing the Overfill Alarm with the Console 9 Testing Over...

Страница 4: ...HLD Setup manual 577013 784 TLS HLD Site Prep manual 577013 879 TLS 4XX Site Prep Manual Contractor Certification Requirements Veeder Root requires the following minimum training certifications for c...

Страница 5: ...ions may only be submitted by selected Distributors Safety Symbols The following safety symbols are used throughout this manual to alert you to important safety hazards and precautions EXPLOSIVE Fuels...

Страница 6: ...rm and Ack switch units are installed in a volatile combustible or explosive Class I Division I and Division II atmosphere Explosion could occur if alarm wires share tank monitor or console probe or s...

Страница 7: ...mensions and Figure 2 shows the Acknowledgment Switch mounting dimensions Figure 1 Overfill Alarm Mounting Dimensions VEEDER ROOT 0 313 8 mm dia 4 holes 2 50 8 mm 1 2 conduit connector 1 6 40 6 mm 4 1...

Страница 8: ...mounting tabs on the housing Acknowledgment Switch 1 Select a mounting location where the Acknowledgment Switch can be easily activated by the tank truck driver In addition consider the ease of routin...

Страница 9: ...power panel 3 Pull one wire from the switch to the TLS Console for connection to the alarm relay 4 Pull one wire for line from the alarm relay in the TLS Console to the power panel 5 Turn power Off an...

Страница 10: ...ground connection is made in accordance with all local codes If using a properly grounded rigid metal conduit or equivalent to enclose the external wiring for the Overfill Alarm the ground hub that te...

Страница 11: ...elay Connection TLS 350 4 Relay Output Module Connection TLS 4XX Overfill Alarm Relay Connector Overfill Alarm without Acknowledge Switch see Figure 4 Overfill Alarm terminal 2 J6 1 J5 1 NO NO NO NO L...

Страница 12: ...at the preset delay time you set above 0 60 seconds The red light will continue to flash until the TEST button is released Setting the Overfill Alarm Horn s Volume Level 1 Locate the adjustment set sc...

Страница 13: ...reapply power to the console and Overfill Alarm If the Overfill Alarm was wired properly the alarm horn will sound immediately followed by the red alarm light flashing 3 Press the RESET button on the...

Страница 14: ......