  Installation

1.

Determine the best location for the temperature sensor in the DEF line. Figure 2 shows a typical temperature 
sensor installation in the DEF dispenser pan furthest from the DEF tank. Each site should be evaluated to 
determine the best location for the temperature sensor.

2.

Install a bushing in the line which has a female 1/2” NPT port at the desired sensor location (see example in 
Figure 2).

Figure 2.   DEF Temperature Sensor Example Installation

3.

Apply non-setting, DEF-compatible thread sealant to the external 1/2” NPT threads on the tube fitting and 
install it into the bushing.

4.

Loosen the nut on the tube fitting and insert the temperature sensor into the tube fitting enough, but not more 
than 6”, to ensure the 1/4” diameter section of the sensor is inside the tube fitting.

5.

Tighten the nut on the tube fitting 1-1/4 turns beyond hand tight.

6.

Figure 3 shows a typical DEF recirculation return line fittings in the DEF pump sump.

When routing the return to the tank it is recommended that the return line be extended near 
the bottom of the tank to avoid any disruption to the tank probe’s readings.

DEF Flow To 
Dispenser
Meter

DEF Dispenser
Pan

DEF Flow 
From Tank

DEF Return
Flow To Tank

DEF Fluid
Temperature
Sensor

Bushing With 
1/2” Female Port

Junction Box
And Seal Off
(Customer
Supplied)

Wiring
To ATG

NOTICE

Содержание DEF

Страница 1: ...Manual No 577014 344 Revision C Installation Manual DEF Recirculation Control...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...ensor Field Wiring 9 Sealing Field Connections 9 Wiring Run Through Rigid Conduit 9 Direct Burial Cable 10 Console Wiring Precautions 10 Connecting Sensor Wiring To The Console 11 Figures Figure 1 DEF...

Страница 4: ...dependently or concurrently with the DEF pump Figure 1 DEF Fluid Temperature Monitoring Components DEF Dispenser DEF Dispenser Heat Trace manufacturer required GFI EPD circuit breaker per NEC Article...

Страница 5: ...install intrinsically safe apparatus use the specific control drawing that appears on the nameplate of the applicable associated apparatus ATG Console The control drawings contain information related...

Страница 6: ...Operator s Manual CLASS I Division 1 Group D CLASS 1 Zone 0 Hazardous Location Intrinsically Safe Apparatus DEF Temperature Sensor Intrinsically Safe Wiring White Brown Black Black I S Rigid Conduit...

Страница 7: ...o alert you to important safety hazards and precautions GENERAL Ensure that all local council and regulations are complied with Also ensure that all recognized safety codes are followed EXPLOSIVE Fuel...

Страница 8: ...energy limited system This system makes the sensors suitable for use in hazardous locations Sensor wiring is intrinsically safe only when connected to the TLS console All sensor wiring must be contai...

Страница 9: ...service this equipment in accordance with these codes regulations and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment ISO STANDARD FOR DEF Th...

Страница 10: ...must be observed Keep fluid away from the motor cable Follow internal instructions Wear protective clothing face and breathing protection protective gloves etc De ploy safety barricades around work a...

Страница 11: ...d install it into the bushing 4 Loosen the nut on the tube fitting and insert the temperature sensor into the tube fitting enough but not more than 6 to ensure the 1 4 diameter section of the sensor i...

Страница 12: ...ugh the seal off box the conduit attaching the junction box to the seal off box and into the junction box 2 Using wire nuts connect the two wires from the sensor to the two wires coming from the conso...

Страница 13: ...nec tors without reprogramming that device 879 38 eps To console Tie wrap Wire nuts From probe sensor or transducer A C B Make sure that the ends of cable sheathing are sub merged in sealant nt t t nt...

Страница 14: ...sensor is NOT grounded 3 Write in the device name for each wire connection on the connector block in the module s wiring label attached to the inside of the door 4 Make sure that you loop the wire nea...

Страница 15: ...m Relay Contact Ratings 120 240 Vac 5A 30 Vdc 5A Fuse ratings 5A 250 Vac Type T Slo Blo TLS 450PLUS TLS XB TLS4 Control Of DEF Piping Heat Trace Circuitry If Required HV Relay Outputs Control Of DEF P...

Страница 16: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: