 Installation

Connecting Sensor Wiring To The Console

11

11

Connecting Sensor Wiring To The Console

intrinsically-safe wiring must enter designated knockouts - refer to the console’s Site 
Prep manual. 

Try not to have too much wire in your console. Pull unneeded wire back into your wiring trough and loop it neatly.

1.

Following the console’s site prep manual instructions open the console doors to access the input connector to 
which you will connect the DEF Temperature Sensor.

2.

Make sure to terminate the sensor wiring ground shield to the ground lug on the module (TLS-450PLUS/TLS-
XB) or in I.S. section of the console (TLS4), as the other end at the sensor is NOT grounded.

3.

Write in the device name for each wire connection on the connector block in the module’s wiring label 
attached to the inside of the door.

4.

Make sure that you loop the wire neatly under the lip of the module. This will keep your wires from interfering 
with the door when it closes. 

5.

Close the console door and access 

Menu>Setup>Device>Sensor

 setup screen and select 

Temp Sensor

 

to setup the new DEF Temperature Sensor.

Figure 6.  Connecting DEF Temperature Sensor To Console

WARNING

TLS-450PLUS/TLS-XB

Observe polarity!

DEF Temperature Sensor Input Wiring

1

2

WHT

BLK

TLS4

DEF Temperature Sensor

WHT

BLK

USM Module

Standard (or Optional)
6-device intrinsically safe
input connector.

(Available intrinsically safe
input connector pair.)

(Available intrinsically safe
input connector pair.)

(   )

(+)

(   )

(+)

(   )

(+)

(   )

(+)

(   )

(+)

(   )

(+)

1

2

3

4

5

6

NOTICE

Observe polarity!

NOTICE

Содержание DEF

Страница 1: ...Manual No 577014 344 Revision C Installation Manual DEF Recirculation Control...

Страница 2: ...f any damages and or shortages within 30 days of receipt of the shipment as stated in our Terms and Conditions VEEDER ROOT S PREFERRED CARRIER 1 Fax Bill of Lading to V R Customer Service at 800 234 5...

Страница 3: ...ensor Field Wiring 9 Sealing Field Connections 9 Wiring Run Through Rigid Conduit 9 Direct Burial Cable 10 Console Wiring Precautions 10 Connecting Sensor Wiring To The Console 11 Figures Figure 1 DEF...

Страница 4: ...dependently or concurrently with the DEF pump Figure 1 DEF Fluid Temperature Monitoring Components DEF Dispenser DEF Dispenser Heat Trace manufacturer required GFI EPD circuit breaker per NEC Article...

Страница 5: ...install intrinsically safe apparatus use the specific control drawing that appears on the nameplate of the applicable associated apparatus ATG Console The control drawings contain information related...

Страница 6: ...Operator s Manual CLASS I Division 1 Group D CLASS 1 Zone 0 Hazardous Location Intrinsically Safe Apparatus DEF Temperature Sensor Intrinsically Safe Wiring White Brown Black Black I S Rigid Conduit...

Страница 7: ...o alert you to important safety hazards and precautions GENERAL Ensure that all local council and regulations are complied with Also ensure that all recognized safety codes are followed EXPLOSIVE Fuel...

Страница 8: ...energy limited system This system makes the sensors suitable for use in hazardous locations Sensor wiring is intrinsically safe only when connected to the TLS console All sensor wiring must be contai...

Страница 9: ...service this equipment in accordance with these codes regulations and standards may lead to legal citations with penalties or affect the safe use and operation of the equipment ISO STANDARD FOR DEF Th...

Страница 10: ...must be observed Keep fluid away from the motor cable Follow internal instructions Wear protective clothing face and breathing protection protective gloves etc De ploy safety barricades around work a...

Страница 11: ...d install it into the bushing 4 Loosen the nut on the tube fitting and insert the temperature sensor into the tube fitting enough but not more than 6 to ensure the 1 4 diameter section of the sensor i...

Страница 12: ...ugh the seal off box the conduit attaching the junction box to the seal off box and into the junction box 2 Using wire nuts connect the two wires from the sensor to the two wires coming from the conso...

Страница 13: ...nec tors without reprogramming that device 879 38 eps To console Tie wrap Wire nuts From probe sensor or transducer A C B Make sure that the ends of cable sheathing are sub merged in sealant nt t t nt...

Страница 14: ...sensor is NOT grounded 3 Write in the device name for each wire connection on the connector block in the module s wiring label attached to the inside of the door 4 Make sure that you loop the wire nea...

Страница 15: ...m Relay Contact Ratings 120 240 Vac 5A 30 Vdc 5A Fuse ratings 5A 250 Vac Type T Slo Blo TLS 450PLUS TLS XB TLS4 Control Of DEF Piping Heat Trace Circuitry If Required HV Relay Outputs Control Of DEF P...

Страница 16: ...For technical support sales or other assistance please visit www veeder com...

Отзывы: