Installation
Connecting Sensor Wiring To The Console
11
11
Connecting Sensor Wiring To The Console
intrinsically-safe wiring must enter designated knockouts - refer to the console’s Site
Prep manual.
Try not to have too much wire in your console. Pull unneeded wire back into your wiring trough and loop it neatly.
1.
Following the console’s site prep manual instructions open the console doors to access the input connector to
which you will connect the DEF Temperature Sensor.
2.
Make sure to terminate the sensor wiring ground shield to the ground lug on the module (TLS-450PLUS/TLS-
XB) or in I.S. section of the console (TLS4), as the other end at the sensor is NOT grounded.
3.
Write in the device name for each wire connection on the connector block in the module’s wiring label
attached to the inside of the door.
4.
Make sure that you loop the wire neatly under the lip of the module. This will keep your wires from interfering
with the door when it closes.
5.
Close the console door and access
Menu>Setup>Device>Sensor
setup screen and select
Temp Sensor
to setup the new DEF Temperature Sensor.
Figure 6. Connecting DEF Temperature Sensor To Console
WARNING
TLS-450PLUS/TLS-XB
Observe polarity!
DEF Temperature Sensor Input Wiring
1
2
WHT
BLK
TLS4
DEF Temperature Sensor
WHT
BLK
USM Module
Standard (or Optional)
6-device intrinsically safe
input connector.
(Available intrinsically safe
input connector pair.)
(Available intrinsically safe
input connector pair.)
( )
(+)
( )
(+)
( )
(+)
( )
(+)
( )
(+)
( )
(+)
1
2
3
4
5
6
NOTICE
Observe polarity!
NOTICE