Vector TLR-D5P-U SeriesTLR-D5P-24 Скачать руководство пользователя страница 15

 

TLR-D5P-U Engineering Manual

 

 

Doc: 70-07-0100, V2.2, Date: 20090201 

©2008 Vector Controls 

Page 15 

Control Parameters (Access Code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Setpoint limitations 

Parameter Description 

Range Default 

CP 00 

Minimum setpoint limit in Heating mode 

-40…60°C (160°F) 

16°C (61°F) 

CP 01 

Maximum setpoint limit in Heating mode 

-40…60°C (160°F) 

24°C (76°F) 

CP 02 

Minimum setpoint limit in Cooling mode 

-40…60°C (160°F) 

18°C (65°F) 

CP 03 

Maximum setpoint limit in Cooling mode 

-40…60°C (160°F) 

30°C (87°F) 

Fan control sequence 

Parameter Description 

Range Default 

CP 04 

Economy temperature shift 

0…10.0K (20°F) 

5.0°C (10°F) 

CP 05 

Switching Span Heating,  

Setting this value to 0 disables the auto fan speed function in heating 

mode 

0…10.0K (20°F) 

0.9°C (1.8°F) 

CP 06 

Switching Span Cooling 
Setting this value to 0 disables the auto fan speed function in cooling 

mode 

0…10.0K (20°F) 

0.7°C (1.4°F) 

CP 07 

Fan Switching Hysteresis 

0…10.0K (20°F) 

0.5°C (1°F) 

CP 08 

Mold Protection: OFF = Disabled, ON = Enabled 

ON, OFF 

OFF 

CP 09 

Delay OFF (Minimum running time) 

0…255 s 

10s 

CP 10 

Delay ON (Minimum stopping time) 

0…255 s 

10s 

CP 11 

2-pipe or 4-pipe system: OFF = 2-pipe, ON = 4-pipe system 

ON, OFF 

OFF 

CP 12 

Dead zone between heating & cooling set point X

DZ

 

0…100°C (200°F) 

1.0°C (2°F) 

CP 13 

Delay on Heat/Cool change over 

0…255 min 

5 min 

Input configuration 

Parameter Description 

Range Default 

CP 14 

External input:  

0 = No external input 
1 = External temperature sensor 
2 = Occupation sensor – Comfort / Economy 
3 = Occupation sensor – Comfort / Off 

4 = Heat / Cool change by open contact. Contact open = Heat 

5 = Heat / Cool change by open contact. Contact open = Cool 
6 = Auto-changeover based on supply temperature 

7 = Auto-changeover based on outside temperature 

8 = Key card with alternative setpoint 

0…8 0 

CP 15 

Activation delay (Minutes) = the time the binary input needs to be open 

before economy/off mode is activated. 

0…255 min 

CP 16 

Auto-changeover limit cooling for supply temperature CP14 = 6 

Auto-changeover limit heating for outside temperature CP14 = 7 

or economy setpoint in heating mode if CP14 = 8 

-40…60°C (160°F) 

16°C (61°F) 

CP 17 

Auto-changeover limit heating for supply temperature CP14 = 6 

Auto-changeover limit cooling for outside temperature CP14 = 7 

or economy setpoint in cooling mode if CP14 = 8 

-40…60°C (160°F) 

28°C (83°F) 

Output configuration 

Parameter Description 

Range Default 

CP 18 

Enable auto heat / cool change based on temperature 

ON, OFF 

OFF 

CP 19 

Reversing valve action: 0 = Off, 1 = Heating, 2 = Cooling 

0…2 

CP 20 

Fan on delay (time the fan runs before stage switch on) 

0…255 s 

30 s 

CP 21 

Fan off delay (time the fan keeps running after stage switch off) 

0…255 s 

90 s 

 
 
 

 

 

Subject to alteration 

Содержание TLR-D5P-U SeriesTLR-D5P-24

Страница 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Страница 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Страница 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Страница 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Страница 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Страница 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Страница 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Страница 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Страница 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Страница 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Страница 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Страница 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Страница 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Страница 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Страница 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Отзывы: