Vector TLR-D5P-U SeriesTLR-D5P-24 Скачать руководство пользователя страница 10

 

TLR-D5P-U Engineering Manual

 

 

Doc: 70-07-0100, V2.2, Date: 20090201 

©2008 Vector Controls 

Page 10 

Setting of parameters 

The TLR-D5P-U is an 

intelligent 

controller and can be adapted to fit perfectly into your application. The control 

operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters are password protected. There are two levels of parameters: User operation parameters for access 
control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert 
levels are different. Only control experts should be given the control parameter password.  
 
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the 

large digits and the software revision in the small digits.  

2.

 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits. 

3.

 

The code for accessing the user parameters is 009 

4.

 

Select this using UP or DOWN buttons. 

5.

 

Press OPTION button after selecting the correct code.  

6.

 

Once logged in, the parameter is displayed immediately. 

7.

 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. The 

MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP or DOWN 
buttons to adjust the value. 

8.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

9.

 

Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button 

is pressed for more than 5 minutes. 

User Parameters 

Parameter Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON (Enabled) 

UP 01 

Enable access to set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable manual control of fan speeds 

ON, OFF 

ON (Enabled) 

UP 03 

Enable change of heating / cooling mode for 2 pipe systems 

ON, OFF 

W00: ON 
(Enabled) 
W01: OFF 
(Disabled) 

UP 04 

Enable access to time programs: 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure:  
0 = off, 1 = on, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy functionality 

ON, OFF 

ON (Economy ) 

UP 07 

Celsius or Fahrenheit, ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor. If required it is possible 

to shift the temperature –10° to +10° in 0.1K steps.  

-10…10 

UP 09 

Enable frost protection 

ON, OFF 

W00 = ON  

(Frost 

Protection) 

W01 = OFF 

(No Frost 

Protection) 

UP 10 

Select contents of Large LCD display in standard mode: 

0…5 

00 = OFF 
01 = Setpoint 
02 = Temperature Input of control loop  
03 = Output Fan Speed 
04 = Clock 

05 = Alternate Temperature Sensor 

UP 11 

Select contents of small LCD display in standard mode 

0…5 

4, 1 

UP 12 

Deluxe only 

Clock display type:  
OFF  = Show 24hour clock 
ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 13 

Deluxe only 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255 = delay in minutes to switch off device if ON/Economy mode is 

activated while the unit is scheduled to be in OFF mode 

0…255 60 

(Min) 

 
 
 

 

Subject to alteration 

Содержание TLR-D5P-U SeriesTLR-D5P-24

Страница 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Страница 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Страница 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Страница 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Страница 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Страница 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Страница 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Страница 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Страница 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Страница 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Страница 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Страница 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Страница 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Страница 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Страница 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Отзывы: