TLR-D5P-U Engineering Manual

 

 

Doc: 70-07-0100, V2.2, Date: 20090201 

©2008 Vector Controls 

Page 1 

TLR-D5P-U Intelligent Package Unit Controller, Base and Terminal 

 

General Description 

The TLR-D5P-U is a stand-alone electronic package unit controller with one control loop. The TLR-D5P-U includes 1 
internal NTC temperature sensor, one open/contact or external NTC temperature input and five binary outputs 
(Relays). A detailed adaptation to local conditions is possible with the use of a simple configuration routine. The TLR-
D5P-U can be configured using the standard operation terminal. No special tools or software is required.  The TLR-
D5P-U has been specifically developed to switch larger fans with switching power of up to 10(6) Amp.  TLR-DP5-U 
includes: 

 

1 package unit control loop 

 

1 internal temperature sensor or external temperature sensor input 

 

1 binary output for fan control 

 

2 binary outputs for cooling 

 

2 binary outputs for heating 

Deluxe Version: 

 

Clock and time schedule functions with special options for schools and universities 

 

Clock keeps running for 48 hours in case of power failure 

 

Display with blue backlight 

 

Infrared remote controller option with special features for Boost and delayed switching on or off 

 
Features 

 

Temperature control for 2- or 4-pipe package units (2 stages fan-supported heating or cooling with reversing 
valve) 

 

Temperature control for 2-pipe package units (fan-supported dual heating or cooling stages) 

 

Temperature control for 4-pipe package units (1 stage fan-supported heating and cooling, optional 2 stage 
heating or cooling)  

 

Relays switching for outputs each up to 10(6)A 

 

Large temperature range from –20°C to 70°C (-4°F to 158°F). 

 

Control for heating, cooling and fan only operation 

 

Adjustable start and stop delays to protect compressors and switching elements 

 

Cost saving option with Economy functionality and set point limitations 

 

External sensor or open contact for remote control, external heat/cool changeover or auto-changeover on 
supply or outdoor temperature with selectable activation limits 

 

Password protected programmable user and control parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode change 

o

 

Access control for heat/cool change and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

 
Applications 

 

Air-only systems: fan supported heating or/and cooling stages e.g. compressors, electric heaters. 

 

Air/water systems: Induction units, fan supported dual coil units for 2- and 4-pipe systems 

 

Содержание TLR-D5P-U SeriesTLR-D5P-24

Страница 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Страница 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Страница 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Страница 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Страница 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Страница 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Страница 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Страница 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Страница 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Страница 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Страница 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Страница 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Страница 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Страница 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Страница 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Отзывы: