TLC3-ECO Economizer
U
SER
C
ONFIGURATION
Doc: 70-00-0660, V1.1, Date: 20170322
© Vector Controls GmbH, Switzerland
Page 7
Subject to alteration
User and display parameters (password 009)
Parameter Description
Range
Default
UP 00
Enable change of operation modes,
ON, OFF
ON (Enabled)
UP 01
Enable change of set points
ON, OFF
ON (Enabled)
UP 02
Parameter not used
ON, OFF
ON
UP 03
Enable manual Heat/Cool change
ON, OFF
W00 = ON
W01 = OFF
UP 04
Enable access to time programs
ON, OFF
ON (Enabled)
UP 05
State after power failure: 0 = OFF, 1 = ON, 2 = Last State
0, 1, 2
2
UP 06
Enable economy (unoccupied) mode.
Shift the setpoint to a lower temperature in winter or higher
temperature in summer in order to save energy. May be activated
through the POWER button.
ON, OFF
ON
(Economy )
UP 07
Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit
ON, OFF
OFF (Celsius)
UP 08
Calibrate internal temperature sensor
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this
feature for field adjustment only as required.)
-10…10
0
UP 09
Calibrate outdoor temperature sensor X1
–10° to +10° in 0.1° steps.
-10…10
0
UP 10
Calibrate external temperature sensor X2
–10° to +10° in 0.1° steps.
-10…10
0
UP 11
Select contents of Large LCD display in standard mode:
0…6
2
Indoor
Temperature
00 = OFF
01 = Setpoint
02 = Control temperature sensor
*1)
03 = Output Mode
04 = Clock
05 = Outdoor sensor (X1)
06 = Alternate sensor
*1)
UP 12
Select contents of small LCD display in standard mode
0…6
Standard:
5Outdoor
Temperature
Deluxe:
4 Clock
00 = OFF
01 = Setpoint
02 = Control temperature Sensor
*1)
03 = Output Mode
04 = Clock
05 = Outdoor sensor (X1)
06 = Alternate sensor
*1)
UP 13
Clock display type: Only available for deluxe version
OFF = Show 24hour clock
ON = Show 12hour clock (AM, PM)
ON, OFF
OFF (24h)
UP 14
Reset timer for override mode: Only available for deluxe version
0
= Reset of override mode is not active.
1…255 = delay in minutes to switch off device if ON/Economy mode
is activated while the unit is scheduled to be in OFF mode
0…255
60 (Min)
*1)
Control temperature sensor or alternate sensor depends on which sensor is selected as control input with CP18.
If CP18 = 1: Control temperature sensor is X2 and alternate sensor is internal temperature sensor
If CP18
1: Control temperature sensor is internal sensor and alternate sensor is X2.