background image

 

TCY-MT-U 

Temperature PID Controller 

 

Doc: 70-00-0176 V1.1, 20100908 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Output Configuration 

Analog Output 

The analog output is fixed to 0-10VDC. The signal range may be configured with parameters. It is thus possible to directly 
set min and maximum flow levels for VAV systems for example.  
To adjust the output for a 2-10VDC signal set the minimum to 20% and keep the maximum at 100%  

Output in standby mode 

The analog output in standby mode may be reduced in order to save energy. The default value is set to 50%.  

VAV applications 

The following description is for 4-pipe systems. The settings apply to TCY-MT4-U.  
In the VAV control sequence, at peak cooling the airflow setpoint is the maximum amount of air the VAV box is set to 
deliver. It may be adjusted through the maximum limit on the analog output in cooling mode (

CP16

). As cooling 

requirements decrease, airflow dwindles until it reaches its minimum setpoint. This setpoint will be based on the airflow 
needed at design cooling and is typically 10% to 15% of maximum cooling airflow. Minimum airflow can be adjusted by 
the minimum limit on the analog output in cooling mode (

CP15

) and in heating mode (

CP13

). When it reaches this 

minimum, the system is in its dead band and is neither heating nor cooling. As the system moves into heating mode, the 
airflow rate increases until it reaches the maximum airflow required for heating mode. This is typically 30 to 50% of 
maximum airflow of cooling mode. The parameter for this is the maximum limitation in heating mode (

CP14

).  

 

 

Configuration parameters for firmware version 1.1 

The TCY-MT-U is preset to work for most applications. For special requirements it can be fine tuned to work ideal with a 
simple parameter setup routine. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore important to use 
a matching product version and parameter set. The Firmware version and revision version can be found when pressing 
simultaneously the 

S

 and 

T

 keys during several seconds. On the upper 7 segment display, the firmware version can be 

found, on the lower 7 segment display the current revision index (or “sub-version”).  

T [°C, F] 

U [V, mA] 

Heating 

Cooling 

100

50

0

Y

H1

, Y

R1 

W

X

DZ

 

Y

C1, 

Y

D1

 

W

heating max: CP14

 

Min cooling: CP15

 

Max cooling: CP16

 

Min heating: CP13

 

Содержание TCY-MT2-U-W2

Страница 1: ...atures and current in and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item N...

Страница 2: ...ondensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 St...

Страница 3: ...re used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple...

Страница 4: ...ndard function If pressed less than 2 sec access for different control modes If pressed for more than 2 sec starts operation level for advanced users Change of time schedules offsets and heat cool set...

Страница 5: ...ns Changing of set points may be disabled with UP01 Manually activating heating or cooling mode Pressing the option button for more than three seconds will toggle Heating Cooling mode Manual Heat Cool...

Страница 6: ...d in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter...

Страница 7: ...roportional part is defined through the p band A narrow P band increases the sensitivity of the controller Typical values used are 1 1 5K for heating 2 3K for cooling sequences The P band should be ex...

Страница 8: ...elay the binary contact has to be open before standby mode is activated This function may be used together with key card switches for hotels or motion detectors for offices Auto change over instructio...

Страница 9: ...minimum limit on the analog output in cooling mode CP15 and in heating mode CP13 When it reaches this minimum the system is in its dead band and is neither heating nor cooling As the system moves int...

Страница 10: ...mode YC1 1 TCY MT2 W2 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W1 0 TCY MT2 W2 1 TCY MT2...

Отзывы: