TCY-MT-U 

Temperature PID Controller 

 

Doc: 70-00-0176 V1.1, 20100908 

© Vector Controls GmbH, Switzerland 

Page 10 

Subject to alteration 

Control Parameters (Access Code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter Description 

Range 

Default 

CP 00 

Minimum setpoint limit in Heating mode 

0…60°C (32..160°F) 

16°C (61°F) 

CP 01 

Maximum setpoint limit in Heating mode 

0…60°C (32..160°F) 

30°C (86°F) 

CP 02 

Minimum setpoint limit in Cooling mode 

0…60°C (32..160°F) 

18°C (65°F) 

CP 03 

Maximum setpoint limit in Cooling mode 

0…60°C (32..160°F) 

30°C (86°F) 

Controls configuration 

Parameter Description 

Range 

Default 

CP 04 

Economy temperature shift 

0…100°C (200°F) 

5.0°C (10°F) 

CP 05 

TCY-MT4 only:  
Dead zone between heating & cooling set point X

DZ

 

0…100°C (200°F) 

1.0°C (2°F) 

CP 06 

TCY-MT4 only: Delay on Heat/Cool change over 

0…255 min 

5 min 

CP 07 

P – band heating X

PH

 

0…100°C (200°F) 

2.0°C (4.0°F) 

CP 08 

P – band cooling X

PC

 

0…100°C (200°F) 

2.0°C (4.0°F) 

CP 09 

K

IH

, Integral gain heating, in 0.1 steps, (TI is fixed to 4s) 

0 disables ID part 
low value = slow reaction 

high value = fast reaction 

0…25.5 0.0 

CP 10 

K

IC

, Integral gain cooling, in 0.1 steps, 0 disables I part 

0…25.5 

0.0 

CP 11 

Configuration of operation mode 
0 = TCY-MT2-W1 = Cooling mode Y

C1 

1 = TCY-MT2-W2 = Heating mode: Y

H1 

2 = TCY-MT2 = Heating and Cooling (2 pipe system), Y

H1

 + Y

C1 

3 = TCY-MT4 = Heating and Cooling (4 pipe system), Y

H1

 + Y

C1 

TCY-MT2: 0 - 2 

TCY-MT4: 0 – 3 

TCY-MT2-W1: 0 
TCY-MT2-W2: 1 

TCY-MT2: 2 

TCY-MT4: 3 

Analog Output 

Parameter Description 

Range 

Default 

CP 12 

Manual override of analog outputs 
OFF = Control mode 

ON = Manual mode (0 – 100%) 

ON, OFF 

OFF 

CP 13 

Min output for AO1 (For TCY-MT4-U = Heating output) 

0 – 100 % 

0% 

CP 14 

Max output for AO1 (For TCY-MT4-U = Heating output) 

0 – 100 % 

100% 

CP 15 

Min output for AO2 (For TCY-MT4-U = Cooling output) 

0 – 100 % 

0% 

CP 16 

Max output for AO2 (For TCY-MT4-U = Cooling output) 

0 – 100 % 

100% 

CP 17 

Maximum limitation in standby mode 

0 – 100 % 

50% 

Input configuration 

Parameter Description 

Range 

Default 

CP 18 

Configuration of remote control input (X1) 

0 = Control input if temperature sensor connected 
1 = Occupation sensor – Comfort / Standby  
2 = Remote enable – Comfort / OFF 
3 = Keycard function: fixed setpoint 

0…3 0 

CP 19 

Activation delay (Minutes) = the time the binary input needs 
to be open before standby/off mode is activated. 

0…255 min 

CP 20 

Fixed setpoint for key card function in heating mode 

0…60°C (32..160°F) 

17°C (63°F) 

CP 21 

Fixed setpoint for key card function in cooling mode 

0…60°C (32..160°F) 

27°C (81°F) 

CP 22 

For TCY-MT2-U only: Enable Auto changeover 

ON, OFF 

OFF 

CP 23 

For TCY-MT2-U only: Auto-changeover limit heating 

0…60°C (32..160°F) 

30°C (86°F) 

CP 24 

For TCY-MT2-U only: Auto changeover limit cooling 

0…60°C (32..160°F) 

15°C (59°F) 

 

Содержание TCY-MT2-U-W2

Страница 1: ...atures and current in and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item N...

Страница 2: ...ondensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 St...

Страница 3: ...re used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple...

Страница 4: ...ndard function If pressed less than 2 sec access for different control modes If pressed for more than 2 sec starts operation level for advanced users Change of time schedules offsets and heat cool set...

Страница 5: ...ns Changing of set points may be disabled with UP01 Manually activating heating or cooling mode Pressing the option button for more than three seconds will toggle Heating Cooling mode Manual Heat Cool...

Страница 6: ...d in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter...

Страница 7: ...roportional part is defined through the p band A narrow P band increases the sensitivity of the controller Typical values used are 1 1 5K for heating 2 3K for cooling sequences The P band should be ex...

Страница 8: ...elay the binary contact has to be open before standby mode is activated This function may be used together with key card switches for hotels or motion detectors for offices Auto change over instructio...

Страница 9: ...minimum limit on the analog output in cooling mode CP15 and in heating mode CP13 When it reaches this minimum the system is in its dead band and is neither heating nor cooling As the system moves int...

Страница 10: ...mode YC1 1 TCY MT2 W2 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W1 0 TCY MT2 W2 1 TCY MT2...