background image

 

 

Remote display OPA-S

 

  

Doc: 70-07-0171, V1.3: 20100421 

Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

Installation 

1.

 

Install the mounting plate straight to the wall or the flush mounting box. Make sure that the nipple with 
the front holding screw is facing to the ground. Make sure the screw heads do not stand out more than 

5 mm of the surface of the mounting plate.  

2.

 

Connect the wires of the terminals to the communication wires according wiring diagram 

3.

 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

4.

 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make 

sure the connection cable does not get into the way. 

5.

 

Tighten the front holding screw to secure the front part to the mounting plate.  

Connection to Base Unit 

 

 

Max. Distance: 50 m using shielded copper wire 

 

Always use shielded copper wire if distance > 20 m and electro magnetic interference is present. 

Setting of configuration parameters 

Intelligent sensors can be adapted to fit perfect into your application. The preparation of the sensing signal is 
defined by parameters.  
The parameters are password protected. The parameters can be changed as follows: 

1.

 

Press UP and DOWN key simultaneously for three seconds. The display will indicate CODE. 

2.

 

Select a password using UP or DOWN keys. Dial 0009 in order to get access to the configuration 

parameters. Press the RIGHT key after selecting the correct password.  

3.

 

Once logged in, choose IP for input configuration or OP for output configuration using UP or DOWN. 

Press the RIGHT key after selection.  

4.

 

The parameters are now displayed. The small digits show the parameter number, the large one its value.  

5.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the RIGHT key. The 

MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP and 
DOWN key to adjust the value. 

6.

 

After you are done, press RIGHT or LEFT key in order to return to the parameter selection level.  

7.

 

Press the LEFT key again so as to leave the menu. The unit will return to normal operation if no key is 
pressed for more than 5 minutes. 

8.

 

The parameters and its values depend on the transmitter. Please use the respective datasheet for the 

list of parameters 

Electrical connections 

Normal cables maybe used for wiring in an EMC-save environment. In an extremely impaired EMC environment 

use only shielded cables. 
The operating voltage must comply with the requirements for safety extra-low voltage (SELV) as per  

EN 60 730. Connect the cable using the four-pin plug provided.  

 